PUMP1 CONFIG
VOLT MIN
• Set the minimum permissible voltage for correct control panel operation.
• If voltage (read) < voltage (set minimum), the control panel enters the MIN VOLTAGE
alarm state.
Default
0 V
Range
0–460 V
Step
1 V
PUMP1 CONFIG
VOLT MAX
• Set the maximum permissible voltage for correct control panel operation.
• If voltage (read) < voltage (set maximum), the control panel enters the MAX VOLTAGE
alarm state.
Default
460 V
Range
0–460 V
Step
1 V
PUMP1 CONFIG
VOLT TOUT
• Set the overvoltage or undervoltage trip delay time.
Default
5 sec
Range
0–20 sec
Step
1 sec
PUMP1 CONFIG
COSFI MIN:0.50
• Set the minimum permissible cosφ to protect the electric pump from dry running
(from the rating plate or measured).
• If the read cosφ is less than the set minimum cosφ, the control panel enters an alarm
state.
Default
0.5
Range
0–1
Step
0.01
PUMP1 CONFIG
COSFI TOUT:5s
• Set the dry running trip delay time.
Default
5 sec
Range
0–20 sec
Step
1 sec
PUMP1 CONFIG
CURR MIN
• Set the minimum permissible current to protect the electric pump from dry running
(from the rating plate or measured).
• If current (read) < current (set minimum), the control panel enters an alarm state due
to DRY RUNNING.
Default
5.0 A
Range
0–18 A
Step
0.1
PUMP1 CONFIG
CURM TOUT
• Set the trip delay time for dry running due to minimum current.
Default
5 sec
Range
0–20 sec
Step
1 sec
PUMP1 CONFIG
MOT PROT:OFF
• Enable or disable motor protection by the thermal cut-outs connected to inputs T1
and T2 (klicson).
Default
OFF
Range
OFF–ON
Step
/
PUMP1 CONFIG
DISABLE:OFF
• Enable or disable electric pump operation when it is under maintenance or has failed.
Default
OFF
Range
OFF–ON
Step
/
If there is an electric pump no. 2
Use the same procedure to configure electric pump no. 2
SELECT
PUMP2 CONFIG
Summary of Contents for E1 MONO