60 | ENGLISH
Configuring MODE 5
SELECT
MODE CONFIG
• Press the
key to confirm the choice and enter the submenu.
9
MODE CONFIG
MODE:1
• Press the
key to enter the submenu and change mode.
6
9
MODE:5
• Press the
or
key to select mode 5
(from modes 1 to 6)
• Press the
key to confirm the choice of MODE:5
• Press the
key to continue with the configuration
9
MODE CONFIG
SETUP
• Press the
key to enter the mode 5 configuration submenu
9
MODE5 CONFIG
P1:3.0 bar
• Set the first activation threshold to a specific pressure.
• This parameter defines the first pressure threshold (P1), above which both
electric pumps are deactivated.
• If the pressure is below this set value (P1) minus the differential value
(DP1), a single pump is activated according to the alternating logic.
Default
3 bar
Range
0–40 bar
Step
0.1
MODE5 CONFIG
DP1:0.5 bar
• Set the differential value (DP1) to a specific pressure.
• This parameter defines the difference between the activation and deactiva-
tion levels with respect to the first activation threshold (P1)
Default
0.5 bar
Range
0-P1
Step
0.1
MODE5 CONFIG
P2:2 bar
• Set the second activation threshold to a specific pressure.
• This parameter defines the second pressure threshold (P2), above which
one of the two electric pumps is deactivated.
• If the pressure is below this set value (P2) minus the differential value
(DP2), the second pump is activated.
Default
2 bar
Range
0–40 bar
Step
0.1
MODE5 CONFIG
DP2:0.5 bar
• Set the differential value (DP2) to a specific pressure.
• This parameter defines the difference between the activation and deactiva-
tion levels with respect to the second activation threshold (P2)
Default
0.5 bar
Range
0-P2
Step
0.1
MODE5 CONFIG
LOGIC:ALTERN.
• If the system has two electric pumps, enable (
ALTERN.
) or disable (
SIN-
GLE
) the alternating logic.
MODE5 CONFIG
DRY LOGIC:COS
• Set whether the dry running stop logic is based on the motor current read-
ing (
CURR
) or cosφ reading (
COS
)
Summary of Contents for E1 MONO