DEFINITION OF THE SWITCH OFF FREQUENCY
(only possible in the AUTOMATIC FUNCTION mode)
• The switch off frequency is a defined minimum frequency threshold and as long as the functional frequency is above this
threshold (namely there will be a demand for water) the inverter will keep the pump switched on. When the frequency of
operation falls below this threshold (namely there will no longer by a demand for water) the inverter stops the pump.
P 3,5
Æ
+
Æ
****
Æ
Z 41,0
Æ
Æ
Z 33,6
Æ
Press together for 5 sec
Present work
frequency
Reduce to
minimum flow
(min. 5 l/min)
Switch-off
frequency
Confirm
SETTING THE PARAMETERS IN THE HIDDEN LISTS
In order to enter into the Hidden Lists where there are the advanced parameters and if it were necessary to modify the factory
values of these same parameters proceed as follows.
• Take the TISSEL-200 OUT OF SERVICE (OFF) by pressing the
key
• Press both the keys at the same time
+
+
HIDDEN LISTS
BASIC
BASIC LIST
Parameters
These are BASIC PARAMETERS which have to be set depending on the
application.
ADV
ADVANCED LIST
Parameters
These are the ADVANCED PARAMETERS which improve the functioning and which
require a detailed knowledge of the system.
INSP
INSPECTION LIST
Parameters
These are the INSPECTION PARAMETERS which enable the user to inspect the
operational status of the system, visualising hours of work, number of starts,
history of the alarms, etc.
TEST
TEST Mode
(accessible only in the OFF
mode)
The TEST mode allows one to start and stop the pump manually (ON/OFF key)
and modify the frequency by 1 Hz at a time. It also allows one to control the
functional parameters of the motor and of the inverter.
ATTENTION: when functioning manually some of the automatic
controls are excluded and the operator must avoid any wrong
manoeuvres.