Boiler Control Instruction & Operation Manual, Rev 1
Page
23
of 64
Installation
Energy Management Interface
The following Parameters are adjustable within the Setup menu of the display. Access Setup menu by
going to the Main Screen > Setup > Display Setup.
READ ALL DIRECTIONS
in this manual
before
entering the Setup Menu.
Display Communication Port Setup:
COM Port:
Com 1
Com 2
Com Port Configure For
Control
EMS
Port Type
Modbus Master
Modbus Slave
Special Notes
Caution
Do not change the baud
rate of this port. Loss of
communication to control
could result.
Note
This is the port to adjust
settings to suit the EMS
System
Modbus Address Range
1-8
1-8
COM Mode (fixed)
RS485
RS485
Baud Rate
38400
38400
Stop Rate (fixed)
1 bit
1 bit
Data Bits (fixed)
8 bit
8 bit
Parity (fixed)
None
None