Boiler Control Instruction & Operation Manual, Rev 1
Page
39
of 64
Setup & Tuning
Parameter Adjustment
Pumps Continued
Factory
Setting
Range / Choices
Parameter and Description
0 Min
0 to 60 Min
Overrun Time: CH Pump (System)
Time that pump runs after demand is satisfied. Used to dissipate heat within the
system.
0 Min
0 to 60 Min
Overrun Time: DHW Pump (also used with Isolation Valve)
Time that pump runs after demand is satisfied. Used to dissipate heat within the
system.
1 Min
10 seconds to 60 Min
Overrun Time: Boiler Pump (Combustion Air Damper and Standby Loss
Damper)
Time that pump runs after demand is satisfied. Used to dissipate heat within the
system.
7 Days
0 to 40 Days
Pump Exercise Interval
The number of days the pump is inactive before the pump will be activated for
the Pump Exercise Time.
20 Sec
0 to 10 Min
Pump Exercise Time
The amount of time the pump runs for exercise. This feature helps prevent pump
seizing due to inactivity periods.
Press HIGH LIMITS to adjust the following parameter.
Factory
Setting
Range / Choices
Parameter and Description
200 (ºF)
60 to 200 (ºF)
Preferred Supply High Limit
Adjustable high limit for the supply temperature. Only adjustable to a number
below the maximum High Limit in the control.
Press STACK LIMIT to adjust the following parameter.
Factory
Setting
Range / Choices
Parameter and Description
200 (ºF)
150 to 230 (ºF)
Preferred Stack High Limit
Adjustable high limit for the stack temperature. Only adjustable to a number
below the maximum Stack Limit in the control.