DIN NANO 3RK
Chapter 5
– Data programming
Rev. 01-16
Page 18
LEVEL 3 PROGRAMMING (Installer level)
To access Level 3 programming, press and hold the UP key (
) and STAND-BY key for over 3 seconds.
When the first programming variable appears:
1. Select the variable you want to change with the key (
) or with the key (
). After selecting the required
variable, it is possible to:
2. View its configuration by pressing the SET key.
3. Edit configuration by pressing and holding the SET key and pressing either the (
) or (
) key.
4. After setting the configuration values, press and hold both the (
) key and the (
) key for a few seconds
until the cell temperature value appears and exit the menu.
5. Any changes made to the variables are saved automatically when the system closes the configuration
menu.
LIST OF LEVEL 3 VARIABLES (Installer Level)
LABEL
MEANING
VALUES
DEFAULT
default
mOd
mOd
Operating mode
selection:
0=Compressor control
with digital outputs
(sideband)
1= Condenser fan control
with digital outputs
(sideband)
2= Condenser fan control
with 0-10V analogue
output (sideband)
2= Compressor control
with 0-10V analogue
output (sideband)
PLEASE NOTE:
the mOd Exchange
involves loading default
settings dedicated on the
variables marked with an
asterisk in the "default
mOd" column
0…3
0
5.10
5.11