USER MANUAL
MAIN INSTALLATION WARNINGS
1.
The installation, maintenance and use of the appliance must be carried out by qualified
personnel able to safely perform the requested operations. Carefully read this manual before
performing any operations and follow all its indications.
2.
Install the appliance as close as possible to the environment where the steam is to be
introduced, namely in the position that guarantees the shorter length of the steam pipe. We
recommend not to exceed 5 meters.
3.
Install the appliance at a height that allows easy access to the control unit for parameter
adjustment and viewing of the display. We recommend a height from the ground of about 1
meter.
4.
Install the appliance at a height that allows easy access to the inside of the humidifier for
cylinder replacement.
5.
Some parts of the humidifier, during operation, may exceed the temperature of 60°C. Make
sure that the surfaces in contact with the humidifier are compatible with these values.
6.
Do not install and use the humidifier near products or objects that can be damaged in contact
with water or the humidity produced.
7.
Avoid placing power cables with signal cables in the same conduit (probes and digital
inputs).
8.
Reduce the lengths of the connecting cables as much as possible, avoiding that the wiring
takes up the spiral shape, which is harmful for possible inductive effects on the electronics.
9.
Install a magneto thermal protection switch, upstream of the humidifier.
10.
All conductors used in the wiring must be appropriately proportioned to support the load they
are to supply.
11.
If it is necessary to extend the probe, it is necessary to use conductors with a suitable section
and in any case not less than 1mm
2
.
12.
Connect a pipe with a diameter of not less than 32mm to the drain hose. This pipe must be
firmly clamped to the drain sleeve and have vertical development for at least the first 50cm.
Make sure that you do not create bottlenecks and do not exceed with its height, at any point in
the path, the level of the drain sleeve.
13.
Use only drinking water for the water load, with a pressure between 1 and 10 bar.