The TA1 sensor requires 3-wires for power and communcation with a TS200(H); as shown
in the diagram above. In many situations you will be able to simply mount the TA1 sensor
on a wall and use the provided 10K internal temperature sensor to detect the temperature
at the desired location.
Follow the guide on page 3 for alternate installation options for the TA1 sensor. The TA1
sensor can be installed at a maximum distance of 500' from a TS200(H). A 10K external
temperature probe can be connected to the TA1 sensor up to 100' away.
We always recommend using a Pelian certified external temperature probe. Contact your
local Pelican Wireless distributor for assistance.
Note:
2
Wiring Diagram
Thermostat
TA1 Sensor
R
23-26V
10K Temperature Sensor
*Range -20˚F to 180˚F
(-28˚C to 82˚C)
+
-
+
-
C
D
R
C
D
T
Terminal Designations
T
D
C
R
R −
24 VAC Power
C −
Common 24 VAC
D −
Data Line
T −
10K Temperature Sensor