For installations where 3-wires already exists or can be run 

from a TS200(H) thermostat to the TA1 sensor. Mount the TA1 

sensor directly on the wall. Connect TA1 sensor’s D, C, and R 

terminals to macthing terminals at TS200(H). 500' maximum 

distance.

Applications:

– Detect temperature inside of an enclosed refrigerator or 

freezer.

– Install the TA1 sensor on the wall with the thermostat placed 

in a secure location.

Remove the internal temperature sensor from the “T” terminal 

of the TA1 sensor.  Connect the external temperature probe to 

the TA1 sensor’s “T” terminal. 100' maximum distance.

Connect the TA1 sensor’s D, C, and R terminals to matching 

terminals of the TS200(H).

The following wiring options should be used to determin the proper wiring approach for your 

application. This guide shows the most common configurations. Contact Pelican Wireless 

Systems for assistance with configurations not shown on this guide. 

3

Up to 100'  

T

D

C

R

Wiring Options:

T

D

C

R

Internal Temperature Sensor

2-Wire External Temperature Probe

Interface a Dry Contact sensor output in order to create an 

alarm notification through your Pelican Site Manager.

Remove provided internal temperature sensor from the “T” 

terminal of the TA1 sensor. Connect the output of the external 

sensor to the TA1 sensor’s “T” terminal.

Connect TA1 sensor’s D, C, and R terminals to matching 

terminals of the TS200(H).

Note: Can be used with normally open or 

normally closed contacts.

T

D

C

R

Interface Dry Contact Relay for Alarm Notification