background image

21

START-UP CLEANING

 WARNING

Following service procedures must be performed 

by qualified service agent. Boiler owner shall not 

attempt these steps. Failure to do so could result in 

death or serious injury.

!

  

It is very important to clean a new steam boiler after it has 

been installed and put into continuous operation. 
This must be done to remove any accumulation of oil, 

grease, sludge, etc., that may have be present in system. 

These substances may cause boiler water to foam and 

surge, producing an unsteady water line, throwing 

water into steam header, and possibly preventing steam 

generation. 
Follow skimming and blow-down steps in order to remove 

contaminants.

Skimming and Blow-down

 WARNING

Burn Scald Hazard. Water temperatures in excess 

of 125°F. Failure to follow these instructions could 

result in death or serious injury.

!

  

New boilers must be skimmed at time of installation to 

remove threading oil and other impurities that float on 

surface of water.

1. 

Remove cap from skimmer female adapter tee and pipe 

to floor drain or bucket. See Figures 4 and 5 page 9. 

Raise water level to skimmer tapping.

2. 

Fire burners to maintain water temperature of 180-

200°F.

3. 

Feed water to boiler to maintain water level. Adjust 

water feed rate to maintain continuous flow of 1 gallon 

per minute. Do not allow boiler to steam.

4. 

Continue skimming until water runs clear. This may 

take several hours.

5. 

Drain boiler completely to remove any foreign material.

6. 

Fill boiler to water line. 
• Fire burners, allow normal steam pressure to build up. 
• Run connection from boiler drain valve to safe 

discharge point outside. 

• Shut off gas burners, open drain valve, allow all of 

water in boiler to drain out.

• Close drain valve. 
• Allow boiler to cool, slowly refill boiler to water line. 
• Repeat this step as many times as necessary until  

blow-down water is clear.

7. 

Following final blow-down, allow boiler to cool.
• Add fresh water slowly up to normal water line. 
• Start burners. 

• Maintain at least 180°F for 15 minutes to remove 

dissolved gasses from fresh water. 

• Shut off burners.

8. 

Allow system to operate for one week to give majority 

of system dirt a chance to work its way back to boiler. 
• Check water in gauge glass. Gauge glass should be 

dry above water line. 

• Water line should not bounce more than one inch 

when boiler is steaming. 

• If you see water droplets carrying over from top of 

gauge glass, or excessive bouncing of water line, 

boiler needs further cleaning. 

• Take water sample and boil it on stove to see if it 

foams. If it does, this indicates boiler needs to be 

cleaned.

NOTICE

Clean water with no additives is essential to proper 

operation of your boiler and heating system. Boiler 

cleaners and chemical cleaning, if used and not 

rinsed properly, may be harmful to the system

.

If cleaning is necessary, repeat skimming and blow-down 

procedure above. A long skim will be all you need to clean 

the boiler. 
In more troublesome cases it may be desirable to flush the 

system while, in very extreme cases, it may be necessary 

to chemically clean and flush heating system.
Consult boiler manufacturer before introducing any 

chemicals into boiler.
Check water level frequently. Be sure top and bottom 

valves on gauge are always open so actual water level is 

shown at all times.

 P/N 1305004, Rev. D [18/03/2015]

Summary of Contents for 16 Series

Page 1: ...ERATION MAINTENANCE MANUAL P N 1305004 Rev D 08 03 2015 MODEL HSID Electronic Intermittent Ignition PENNCO BOILERS 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com MODELS 1603HSID 1604HSID 1605HSID 1606HSID 1607HSID 1608HSID 1609HSID ...

Page 2: ...Inches Intermittent Ignition w Vent Damper Flue Diameter A Width 1603HSID 5 11 1604HSID 6 14 1605HSID 6 17 1606HSID 7 21 1607HSID 7 24 1608HSID 7 27 1609HSID 7 30 Add 5 to height for Vent Damper 1 Add model number suffix P for Propane Gas P N 1305004 Rev D 18 03 2015 ...

Page 3: ... Rating Mbh Net AHRI Rating Sq Ft 1 1603HSID 3 Natural Gas 75 62 82 7 47 196 Propane 70 58 82 7 44 183 1 1604HSID 4 Natural Gas 112 91 82 0 68 283 Propane 105 85 80 4 64 267 1 1605HSID 5 Natural Gas 150 122 82 0 92 383 Propane 140 114 80 6 86 358 1 1606HSID 6 Natural Gas 187 153 82 0 115 479 Propane 175 143 80 9 107 446 1 1607HSID 7 Natural Gas 225 183 82 0 137 571 Propane 210 171 81 1 128 533 1 1...

Page 4: ...ring any obligation whatsoever Introduction Boiler is designed for use in closed heating systems where all steam is returned as condensate and make up water is minimal Boiler is not designed for or intended for use in open systems using 100 make up water Prior to Installation Verify correct boiler for type of gas being used natural or propane See Rating Plate Verify boiler size and dimensions See ...

Page 5: ...s appliance with improper methods or materials could result in death or serious injury due to fire or to asphyxiation from poisonous gases such as carbon monoxide which is odorless and invisible WARNING Fire explosion asphyxiation hazard Keep boiler area clear and free from combustible materials gasoline and other flammable vapors and liquids Modification substitution or elimination of factory equ...

Page 6: ... use Boiler location should not interfere with proper circulation of air Introduce outside air if normal infiltration does not provide necessary air Fresh Air for Combustion on page 11 6 Notify owner to keep air passages free of obstruction Ventilating and combustion air must enter boiler room without restrictions 7 Install boiler so automatic gas ignition system components are protected from wate...

Page 7: ...obstruction in discharge line Terminate freely to atmosphere where any discharge will be clearly visible and at no risk of freezing Allow complete drainage of valve and discharge line Install safety valve with spindle in vertical position Do not install shutoff valve between boiler and safety valve Support safety valve discharge piping Be short and straight as possible Terminate with plain end not...

Page 8: ...er one for each main 6 All boilers in gravity return systems must be equipped with a Hartford Loop as shown in Figure 5 7 When piping the vertical risers from the boiler to the header the bottom of the header must be a minimum of 24 inches above the water level line on the right side of the boiler 8 Steam riser s and header shall be 2 pipe size 9 Equalizer line shall be minimum 1 pipe size 10 The ...

Page 9: ...9 Figure 4 Recommended Near Boiler Piping Using One Supply Tapping SYSTEM PIPING P N 1305004 Rev D 18 03 2015 ...

Page 10: ... PIPING Figure 6 Chilled Water Piping VALVES A B OPEN FOR HEATING CLOSE FOR COOLING VALVES C D CLOSE FOR HEATING OPEN FOR COOLING Figure 5 Recommended Near Boiler Piping Using Two Supply Tappings P N 1305004 Rev D 18 03 2015 ...

Page 11: ... Room volume is greater than 21 cubic feet divided by ACH air changes per hour x Total Input Mbh C Refer to National Fuel Gas Code for opening requirements between connected indoor spaces All Outdoor Air Provide permanent opening s communicating directly or by ducts with outdoors A Two Permanent Opening Method Provide opening commencing within 12 inches of top and second opening commencing within ...

Page 12: ...nger than 3 4 the chimney height HT Figure 7 page 13 Vent Pipe Fasten sections of vent pipe with 3 sheet metal screws at each joint to make piping rigid Support horizontal portions of vent system to prevent sagging Use stovepipe wires or metal strapping every 5 to support pipe from above Vent pipe through crawl space use double wall vent pipe Vent pipe passing through combustible wall or partition...

Page 13: ... appliance to their previous conditions of use 7 Any improper operation of the common venting system should be corrected so the installation conforms with the National Fuel Gas Code ANSI Z223 1 NFPA 54 When re sizing any portion of the common venting system the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Chapter 13 of the Natio...

Page 14: ...nt damper troubleshooting guide refer to manual packaged with vent damper Horizontal Installation To Boiler Vent Damper To Chimney NO NO YES YES Flow Install vent damper with actuator to sides of vent only Do not mount above or below vent To Chimney Flow Vent Damper To Boiler Actuator may be installer in any position Figure 9 Alternate Vent Damper Installation Do Not Install Here Caution Do not in...

Page 15: ...cessive vibrations and prevent strain on gas connection Gas valve will not support piping weight Use thread joint compound pipe dope suitable for natural and liquefied petroleum gas Install field sourced manual main shutoff valve ground joint union and sediment trap upstream of gas valve See Figure 11 DANGER Fire Hazard Do not use matches candles open flames or other methods providing ignition sou...

Page 16: ...res are black One wire is located on secondary of 24 volt transformer second wire is located on pressure limit control F Boilers with CG400 probe type low water cut off one wire is green and is located on terminal P2 of CG400 second wire is black and located on pressure limit control VENT DAMPER Boiler is equipped with factory wired 4 pin molex harness that plugs into 4 pin molex receptacle inside...

Page 17: ...ly and turn clockwise to OFF Do not force For Your Safety Read Before Operating WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life This appliance is equipped with an ignition device which automatically lights burner Do NOT try to light this burner by hand Before operating smell all around appliance area for...

Page 18: ...e of boiler Determine water level when boiler is off and cold when all water in the system is inside the boiler and return piping below water line and everything above water line is air no steam When boiler is making steam water level drops two to three inches below normal water line WARNING Burn Hazard Never run water into a hot empty boiler Failure to follow these instructions could result in de...

Page 19: ...n softer blue outer mantel with no yellow Remain still when observing main burner flames Check main burner orifices burner throat and flame ports for dust and lint obstruction if flame appearance is not correct Remove rollout shield if necessary to observe main burner flames Replace rollout shield after observation Gas Valve Safety Shutdown Test 1 Test ignition system safety shutoff device after p...

Page 20: ...rn thermostat to call for heat C Gas valve opens for approximately 10 seconds time delay on probe type LWCO gas valve will close and red indicator illuminates on LWCO D When water is restored it waits 30 seconds before reactivating burner circuit Boiler Equipped With Optional WF 2U 24 Water Feeder E Continue thermostat call for heat after low water cut off recognizes low water condition F One minu...

Page 21: ...nection from boiler drain valve to safe discharge point outside Shut off gas burners open drain valve allow all of water in boiler to drain out Close drain valve Allow boiler to cool slowly refill boiler to water line Repeat this step as many times as necessary until blow down water is clear 7 Following final blow down allow boiler to cool Add fresh water slowly up to normal water line Start burne...

Page 22: ...F RTV silicone to four mounting surface flanges of flue collector Mount flue collector on heat exchanger Tighten nuts and bolts 6 Seal front edge and four corners of flue collector to heat exchanger with silicone sealant 7 Use flashlight to verify there are no gaps in silicone seal 8 Install draft diverter vent damper vent pipe and jacket top and front cover 9 Reassemble all parts 10 Check tightne...

Page 23: ...out switch blown Have your service technician check heat exchanger for blockage Chimney flue is blocked Spill switch contacts open requiring manual reset of spill switch Have your service technician check and correct chimney problem Vent damper not operating Consult troubleshooting guide packaged with vent damper IF BURNER IS NOISY Gas input amount is incorrect Contact your service technician IF W...

Page 24: ...ust be replaced it must be replaced with type 105 C Thermoplastic wire or its equivalent Figure 13 Wiring Diagrams For Boilers With CG400 Probe Type Low Water Cut Off Shown CG400 PS802 CG400 N 2 H 1 C P1 W P2 B A Terminals PS802 To CG400 Cross Reference P N 1305004 Rev D 18 03 2015 ...

Page 25: ...inal wire as supplied with this appliance must be replaced it must be replaced with type 105 C Thermoplastic wire or its equivalent Figure 17 Wiring Diagrams For Boilers With 67D 1 Float Type Low Water Cut Off P N 1305004 Rev D 18 03 2015 ...

Page 26: ...24 water feeder maybe used with either of the low water cutoffs listed Water feeder maintains safe minimum water level Keeps boiler running by compensating for minor evaporative steam leaks and prevents freeze ups if homeowners are away and return line leaks McDonnell and Miller Model 101 water feeders may be used however water feed rates are too high and need to be regulated or throttled and wiri...

Page 27: ...27 REPAIR PARTS P N 1305004 Rev D 18 03 2015 ...

Page 28: ...28 REPAIR PARTS P N 1305004 Rev D 18 03 2015 ...

Page 29: ...29 REPAIR PARTS P N 1305004 Rev D 18 03 2015 ...

Page 30: ...30 REPAIR PARTS Safety Relief Valve 14 11 NPT X 4 Nipple PF 033 02 CG400 LOW WATER CUT OFF 240009340 P N 1305004 Rev D 18 03 2015 ...

Page 31: ...31 Date Service Performed Company Name Tech Initials Company Address Phone P N 1305004 Rev D 18 03 2015 ...

Page 32: ...verride which is provided primarily to permit the use of an external energy management system that serves the same function THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITIONS IS TRUE An external energy management system is installed that reduces the boiler water temperature as the heating load decreases This boiler is not used for any space heating This boiler is part o...

Reviews: