background image

TABLE OF CONTENTS

MANUAL OVERVIEW ................................................................ 2
SAFETY INFORMATION ............................................................ 2
TYPICAL TOOLS AND FITTINGS REQUIRED ............................ 3
VALVE DIMENSIONS ................................................................ 3
VALVE LAYOUT ......................................................................... 4
SPECIFICATIONS ..................................................................... 4
EQUIPMENT INSTALLATION .................................................... 4
SYSTEM STARTUP .................................................................... 6
INSTALLATION CHECKLIST ..................................................... 6
CONTROL OPERATION AND LAYOUT ...................................... 6
PROGRAMMING THE 606F DEMAND CONTROL ..................... 7
REMOTE REGENERATION ....................................................... 8
VALVE ASSEMBLY .................................................................... 9
TROUBLESHOOTING ................................................................ 10
FLOW DIAGRAMS ..................................................................... 11
FLOW PERFORMANCE DATA CHARTS .................................... 12

MANUAL OVERVIEW

How To Use This Manual

This manual is designed to guide the installer through the 

process of installing and starting the filter.
This manual is a reference and will not include every system 

installation situation. The person installing this equipment 

should have:

•  Knowledge in water filter installation
•  Basic plumbing skills

Icons That Appear In This Manual

WARNING:

 Failure to follow this instruction can result in 

personal injury or damage to the equipment.

NOTE: This will make the process easier if followed.

Inspection

Inspect the unit for damage or missing parts. 

SAFETY INFORMATION

Electrical

•  There are no user-serviceable parts in the AC adapter, 

motor, or controller. In the event of a failure, these should 

be replaced.

•  All electrical connections must be completed according to 

local codes.

•  Use only the power AC adapter that is supplied.
•  The power outlet must be grounded and always on.
•  To disconnect power, unplug the AC adapter from its 

power source.

•  Install an appropriate grounding strap across the inlet 

and outlet piping of the water system to ensure proper 

grounding is maintained.

Mechanical

•  Do not use petroleum-based lubricants such as 

petroleum jelly, oils, or hydrocarbon-based lubricants. 

Use only 100% silicone lubricants.

•  All plastic connections should be hand tightened. 

Plumber tape should be used on connections that do not 

use an O-ring seal. Do not use pliers or pipe wrenches.

•  All plumbing must be completed according to local codes.
•  Soldering of the plumbing should be done before 

connecting to the valve. Excessive heat will cause interior 

damage to the valve.

•  Observe local drain line requirements.
•  Do not use lead-based solder for sweat solder 

connections.

•  Do not support the weight of the system on the control 

valve fittings, plumbing, or the bypass.

•  It is not recommended to use sealants on the threads. 

Use plumber tape (PTFE) on all threads.

General

•  Observe all warnings that appear in this manual.
•  This system is not intended to be used for treating water 

that is microbiologically unsafe or of unknown quality 

without adequate disinfection before or after the system.

•  Keep the unit in the upright position. Do not turn on side,  

upside down, or drop. Turning the tank upside down will 

cause media to enter the valve.

•  Operating ambient temperature is between 34°F (1°C) 

and 120°F (49°C).

•  Operating water temperature is between 34°F (1°C) and 

100°F (38°C).

•  Working water pressure range is 20 to 125 psi  

(1.38 to 8.61 bar). 

•  Follow state and local codes for water testing. 
•  When filling media tank, do not open water valve 

completely. Fill tank slowly to prevent media from exiting 

the tank.

•  Always make modifications to house plumbing first. 

Connect to valve last.

•  Plastic parts and O-rings may be damaged by heat and 

solvents. When constructing plumbing connections, allow 

heated parts to cool and protect parts from solvents.

Location Selection

Location of a water treatment system is important. The 

following conditions are required:

•  Level platform or floor.
•  Constant electrical supply to operate the controller.
•  Total minimum pipe run to water heater of ten feet (three 

meters) to prevent backup of hot water into system.

•  Local drain or tub for discharge as close as possible.
•  Water line connections with shutoff or bypass valves.
•  Room to access equipment for maintenance.

2 • 

Autotrol

®

 363 Demand Automatic Filter Valve

Summary of Contents for AUTOTROL 363

Page 1: ...AUTOTROL 363 DEMAND AUTOMATIC FILTER VALVE Service Manual 2014 Pentair Residential Filtration LLC www pentairaqua com pro...

Page 2: ...ing seal Do not use pliers or pipe wrenches All plumbing must be completed according to local codes Soldering of the plumbing should be done before connecting to the valve Excessive heat will cause in...

Page 3: ...degrade to cause system failures Temperature Extreme hot or cold temperatures may cause damage to the valve or controller Freezing temperatures will freeze the water in the valve This will cause phys...

Page 4: ...softener should be installed downstream of this system Grounding the Plumbing It is important that the plumbing system be electrically grounded When a water treatment system is installed a nonmetallic...

Page 5: ...to 6 feet 1 8 m providing the run does not exceed 15 feet 4 6 m and water pressure at the filter is not less than 40 psi 2 76 bar Elevation can increase by 2 feet 61 cm for each additional 10 psi 69 b...

Page 6: ...media tank Turn on the water supply after five minutes Check for leaks The system is now fully operational INSTALLATION CHECKLIST ___ Read the owner s installation manual ___ Follow all safety guideli...

Page 7: ...set a time duration between cleaning cycles to ensure proper function of the filter in the event of a flow sensor malfunction press and hold and for three seconds The value in days between cleaning c...

Page 8: ...en and C 4 Repeat steps 2 and 3 to cycle through each position Quick Cycle to Service Position Simultaneously press and and hold for three seconds during any cleaning cycle step The control will skip...

Page 9: ...PT 360 Fltr 4002469 Kit DLFC 20GPM NPT 360 Fltr 4002476 Kit DLFC 4 0GPM BSP 360 Fltr 4002477 Kit DLFC 4 5GPM BSP 360 Fltr 4002478 Kit DLFC 5 0GPM BSP 360 Fltr 4002479 Kit DLFC 6 0GPM BSP 360 Fltr 4002...

Page 10: ...haft slots If motor continues to rotate indefinitely replace the following components in this order 1 Motor Assembly Optical Sensor 2 Control System Problem Possible Cause Solution Flowing or dripping...

Page 11: ...kwash Media Tank Inlet Outlet 1 4 3 2 BACKWASH Drain Drain Control FAST RINSE Untreated Water Rinse Media Tank Inlet Outlet 4 3 Drain Control 1 2 Drain Valve No 1 Closed 2 Open 3 Closed 4 Closed Valve...

Page 12: ...TA CHARTS 12 Autotrol 363 Demand Automatic Filter Valve 0 5 10 15 20 25 30 1 6 11 16 21 26 PRESSURE DROP IN PSI FLOW IN GPM Service Cv 5 43 0 5 10 15 20 25 30 35 1 6 11 16 21 PRESSURE DROP IN PSI FLOW...

Page 13: ...egistered marks of their respective owners Because we are continuously improving our products and services Pentair reserves the right to change specifications without prior notice Pentair is an equal...

Reviews: