FLECK
2850S Service Manual
•
5
5. In any event, conditioned water may be drawn after rinse
water stops flowing from the water conditioner drain line.
How to Adjust Regeneration Time
1. Disconnect the power source.
2. Locate the three screws behind the manual regeneration
knob by pushing the red button in and rotating the 24 hour
dial until each screw appears in the cut out portion of the
manual regeneration knob.
3. Loosen each screw slightly to release the pressure on the
time plate from the 24-hour gear.
4. Locate the regeneration time pointer on the inside of the
24 hour dial in the cut out.
5. Turn the time plate so the desired regeneration time
aligns next to the raised arrow.
6. Push the red button in and rotate the 24 hour dial. Tighten
each of the three screws.
7. Push the red button and locate the pointer one more time
to ensure the desired regeneration time is correct.
8. Reset the time of day and restore power to the unit.
61502-3200 Rev A
Figure 2
3210 TIMER SETTING PROCEDURE
Typical Programming Procedure
Calculate the gallon capacity of the system, subtract the
necessary reserve requirement and set the gallons available
opposite the small white dot on the program wheel
gear (Figure 4).
NOTE: Drawing shows 8,750 gallon setting. The capacity
(gallons) arrow (15) shows zero gallons remaining.
The unit will regenerate tonight at the set
regeneration time.
How To Set The Time Of Day
1. Press and hold the red button in to disengage the drive gear.
2. Turn the large gear until the actual time of day is opposite
the time of day pointer.
3. Release the red button to again engage the drive gear.
How To Manually Regenerate Your Water Conditioner At
Any Time
1. Turn the manual regeneration knob clockwise.
2. This slight movement of the manual regeneration knob
engages the program wheel and starts the regeneration
program.
3. The black center knob will make one revolution in the
following approximately three hours and stop in the position
shown in the drawing.
4. Even though it takes three hours for this center knob to
complete one revolution, the regeneration cycle of your unit
might be set for only one half of this time.
5. In any event, conditioned water may be drawn after rinse
water stops flowing from the water conditioner drain line.
Immediate Regeneration Timers
These timers do not have a 24 hour gear. Setting the gallons
on the program wheel and manual regeneration procedure are
the same as previous instructions. The timer will regenerate as
soon as the capacity gallons reaches zero.
NOTE: The program wheel to the left may be different than
the program wheel on the product.
NOTE: To set meter capacity rotate manual knob one - 360°
revolution to set gallonage.
61502-3200 Rev A
Figure 3
STARTUP INSTRUCTIONS
CONTINUED
Summary of Contents for Fleck 2850s
Page 1: ...waterpurification pentair com FLECK 2850S SERVICE MANUAL...
Page 7: ...FLECK 2850S Service Manual 7 THIS PAGE LEFT INTENTIONALLY BLANK...
Page 8: ...8 FLECK 2850S Service Manual 37 615023200 Rev A 3200 TIME CLOCK TIMER ASSEMBLY 36 38...
Page 10: ...10 FLECK 2850S Service Manual 3210 METER DELAYED TIMER ASSEMBLY 41 42 61502 3210 Rev A 40 43...
Page 21: ...FLECK 2850S Service Manual 21 THIS PAGE LEFT INTENTIONALLY BLANK...
Page 26: ...26 FLECK 2850S Service Manual 1700 BRINE SYSTEM ASSEMBLY 60034 Rev D 28 29...
Page 34: ...34 FLECK 2850S Service Manual 2310 SAFETY BRINE VALVE...
Page 37: ...FLECK 2850S Service Manual 37 THIS PAGE LEFT INTENTIONALLY BLANK...
Page 41: ...FLECK 2850S Service Manual 41 THIS PAGE LEFT INTENTIONALLY BLANK...
Page 44: ...44 FLECK 2850S Service Manual DIMENSIONAL DRAWING...
Page 55: ...FLECK 2850S Service Manual 55...