Installer Manual Fleck 5812 - XTR - Maintenance
Ref. MKT-IM-019 / E - 14.10.2019
103 / 132
* Wear parts - durability strongly affected by raw water quality and regeneration frequency.
** Electronic parts – durability strongly affected by power source quality and stability.
*** Elastomer durability is strongly affected by raw water concentration in chlorine and its derivative.
**** Seals & Spacer cartridge is equipped with O-rings that ensure watertightness by compression, therefore by unmounting/
remounting the same cartridge may cause it not to be watertight anymore, each time the seals & and spacer cartridge is
extracted from the valve body it must be pre-placed by a new one. Note that extraction the piston may also extract the Seals
and spacer cartridge at the same time for this reason it not advised to unmount the piston, clean and lubricate it with silicon
grease as with former residential fleck valves for the regular maintenance, but only to replace it at least every 3 years.
O-rings***
Check for
watertightness
/clean or
replace in case
of leakage
Check for
watertightness
/clean or
replace in case
of leakage
Check for
watertightness
/clean or
replace in case
of leakage
Check for
watertightness
/clean or
replace in case
of leakage
Check for
watertightness
/clean or
replace in case
of leakage
Motor
Check
Check
Check
Check
Replace
Optical sensor
Check
Check
Check
Check
Replace
Gearing
Check
Check
Check
Check
Check/ replace
if necessary
Encoding
wheel
Clean
Clean
Clean
Clean
Clean
Inlet hardness
Check
Check
Check
Check
Check
Residual
hardness
Check/adapt
mixing screw if
necessary
Check/adapt
mixing screw if
necessary
Check/adapt
mixing screw if
necessary
Check/adapt
mixing screw if
necessary
Check/adapt
mixing screw if
necessary
Electronic/
settings**
Check
Check
Check
Check
Check/ replace
if necessary
Transformer**
Check
Check
Check
Check
Check/ replace
if necessary
Meter* (if
present)
Check and
Clean
Check and
Clean
Check and
Clean
Check and
Clean
Replace
Meter cable (if
present)
Check
Check
Check
Check
Replace
Valve
watertightness
Check
Check
Check
Check
Check
Valve to piping
watertightness
Check
Check
Check
Check
Check
Items
1 year
2 year
3 year
4 year
5 year
Summary of Contents for FLECK 5812 XTR
Page 1: ...INSTALLER MANUAL WATER PURIFICATION FLECK 5812 XTR...
Page 18: ...Installer Manual Fleck 5812 XTR Description 18 132 Ref MKT IM 019 E 14 10 2019 3 2 2 Base 4...
Page 108: ...Installer Manual Fleck 5812 XTR Maintenance 108 132 Ref MKT IM 019 E 14 10 2019...
Page 110: ...Installer Manual Fleck 5812 XTR Maintenance 110 132 Ref MKT IM 019 E 14 10 2019...
Page 132: ...www pentairaquaeurope com...