Installer Manual Fleck 5812 - XTR - Troubleshooting
Ref. MKT-IM-019 / E - 14.10.2019
121 / 132
Flow meter error
Continuous Flow
The flow meter has
reported continuous
flow for more than
24 hours.
Error will clear when flow to meter drops below 0.5
GPM or 1 LPM. If continuous flow is expected, turn
plumbing leak detection off in Master Settings.
Over current
Motor over current
detected
Motor drew too much
current.
Attempt to perform a manual regeneration. If error
continues, call technical support.
Flow meter error
No flow detected
No flow has been
detected for 7 days.
Error will clear when a flow pulse is detected. Check to
ensure meter cable is properly installed and meter
spins freely. Clear meter of debris if necessary. If error
continues, call technical support.
No regeneration
for 100 days
The valve has not
regenerated in more
than 100 days.
Initiate a regeneration see “Troubleshooting”,
page 118.
Service Interval
Service Interval
controller has expired.
From within Master Settings, navigate to the
Assistance/Mainten. Interval screen and set a new
Service Interval time.
Memory
Corruption Error
Internal memory
inconsistent or
corrupted.
1. Cycle power to XTR2 controller.
2. Drain supercap and cycle power to XTR2 controller.
3. If error continues, call technical support.
Motor Stall
Motor Run-On
No changes
detected in the
optical sensor for
6 seconds
No state changes in
the optical sensor are
detected for
six seconds.
Unplug the unit and plug back in. Allow the control to
attempt to find position again.
Verify the optical sensor is in place with the wires
connected to the circuit board. Verify the motor and
drive train components are in good condition and
assembled properly. Check the valve and verify that the
piston travels freely. Replace/reassemble the various
components as necessary.
Plug the unit back in and observe its behaviour. If the
error reoccurs, unplug the unit, put it into bypass and
contact technical support.
Error screen
display
Cause
Reset and recovery
Summary of Contents for FLECK 5812 XTR
Page 1: ...INSTALLER MANUAL WATER PURIFICATION FLECK 5812 XTR...
Page 18: ...Installer Manual Fleck 5812 XTR Description 18 132 Ref MKT IM 019 E 14 10 2019 3 2 2 Base 4...
Page 108: ...Installer Manual Fleck 5812 XTR Maintenance 108 132 Ref MKT IM 019 E 14 10 2019...
Page 110: ...Installer Manual Fleck 5812 XTR Maintenance 110 132 Ref MKT IM 019 E 14 10 2019...
Page 132: ...www pentairaquaeurope com...