5.3. Installation
environment
5.3.1. General
•
Use only brine salts designed for water softening. Do not use ice melt salt, block, or rock salts;
•
keep the media tank in the upright position. Do not turn on its side, upside down, or drop. Turning
the tank upside down may cause media to enter the valve or plug the upper screen;
•
follow State and local codes for water testing. Do not use water that is micro-biologically unsafe
or of unknown quality;
•
when installing the water connection (bypass or manifold) first connect to the plumbing system.
Allow heated parts to cool and cemented parts to set before installing any plastic parts. Do not
get primer or solvent on O-rings, nuts, or the valve.
5.3.2. Water
•
Water temperature must not exceed 43°C;
•
a minimum of 1.4 bar (dynamic pressure on injector) of water pressure is required for the
regeneration valve to operate effectively.
Mandatory
Do not exceed a maximum of 8.6 bar inlet pressure. Should this happen or be subject to
happen, it is necessary to install a pressure regulator upstream the system.
5.3.3. Electrical
There are no user-serviceable parts in the AC/DC transformer, motor, or controller. In the event of a
failure, these should be replaced.
•
All electrical connections must be completed according to local codes;
•
use only the power AC/DC transformer that is supplied;
Mandatory
The use of any other power transformer than the one supplied void the warranty of all
electronic parts of the valve.
•
the power outlet must be grounded;
•
to disconnect power, unplug the AC/DC transformer from its power source;
•
an uninterrupted current supply is required. Please make sure that the voltage supply is
compatible with the unit before installation;
•
make sure the controller power source is plugged in;
•
if the electrical cable is damaged, it must imperatively be replaced by qualified personnel.
Summary of Contents for FLECK 5812 XTR
Page 1: ...INSTALLER MANUAL WATER PURIFICATION FLECK 5812 XTR...
Page 18: ...Installer Manual Fleck 5812 XTR Description 18 132 Ref MKT IM 019 E 14 10 2019 3 2 2 Base 4...
Page 108: ...Installer Manual Fleck 5812 XTR Maintenance 108 132 Ref MKT IM 019 E 14 10 2019...
Page 110: ...Installer Manual Fleck 5812 XTR Maintenance 110 132 Ref MKT IM 019 E 14 10 2019...
Page 132: ...www pentairaquaeurope com...