Installer Manual Fleck 5812 - XTR - Programming
70 / 132
Ref. MKT-IM-019 / E - 14.10.2019
Relay output
Aux.1/Aux.2
Alarm Based
Cycle Based
Time Based
Volume Based
Off
For cycle based relays, select the cycle steps
on which the relays will turn on. For time
based relays, two start/end times can be
selected for each relay. Relay times are based
on total regeneration cycle time.
Volume based relays can be programmed
from one gallons/liters to the full system
volume capacity. Duration can be set from one
second to two hours. Volume based option is
not available when regeneration type is set to
time clock. Alarm based relays will turn on
when an alarm condition is met, and will turn
off when the alarm is cleared.
Meter
Meter type
0.75" Paddle
1.00" Paddle
1.25" Turbine
1.50" Paddle
1.50" Turbine
2.00" Paddle
3.00" Paddle
Generic
Only available when meter regeneration type
is selected.
Select the type of meter installed with the
system. A generic option is available if the
installed meter does not match any other
selection. Selecting the generic meter type
requires setting the number of pulses per
gallon or liter to ensure proper metering.
The standard setting for 5812-XTR is 1.25"
Turbine.
Meter
Generic
0,1 - 999.9 pulses
per gallon
1 - 1500 pulses
per litre
Only available when generic meter type is
selected.
Continuous
flow detect
ON
OFF
If set ON, gives an alarm if continuous flow is
detected at the outlet.
Setting
review
Displays a summary of all programmed settings.
Water Saver
Regen
Water saver
regen.
OFF
Remote
regeneration
Remote
signal
duration
1 - 255 seconds
OFF
Set the timing for contact closure in seconds
in order to trigger the regeneration.
Screen name
Parameters
Values
Notes
Summary of Contents for FLECK 5812 XTR
Page 1: ...INSTALLER MANUAL WATER PURIFICATION FLECK 5812 XTR...
Page 18: ...Installer Manual Fleck 5812 XTR Description 18 132 Ref MKT IM 019 E 14 10 2019 3 2 2 Base 4...
Page 108: ...Installer Manual Fleck 5812 XTR Maintenance 108 132 Ref MKT IM 019 E 14 10 2019...
Page 110: ...Installer Manual Fleck 5812 XTR Maintenance 110 132 Ref MKT IM 019 E 14 10 2019...
Page 132: ...www pentairaquaeurope com...