Installer Manual Fleck 5812 - XTR - Programming
Ref. MKT-IM-019 / E - 14.10.2019
71 / 132
6.3.3. Format screen
From the master settings screen press the
format
button to display the format screen.
language
: Displays the language used on the controller: English, French, German, Italian, Spanish,
Dutch or Portuguese.
units
: Contains settings for the unit type (either US or Metric) to be used in the controller.
Cl generation
Low salt
Cl generation
/
Low salt
OFF
ON
Low salt detect.
This parameter will not be available for filter
regeneration types.
On the valves of series 5810 and 5812,
cl generation/low salt must be set OFF
because the chlorine cell kit managed by the
XTR is not available for those valves.
If set ON, chlorine generation together with
low salt detection will be performed during
brine draw cycle.
If set "Low salt detec.", only low salt detection
will be performed during brine cycle.
Regen
interval
1 - 255
Regeneration
Only available when cl generation/low salt is
set ON.
This parameter determines the regeneration
frequency on which there will be chlorine
generation.
Low salt detection will be performed during
regenerations indifferently of the frequency
set for cl generation.
Salt alarm will not avoid scheduled
regenerations to be performed.
Screen name
Parameters
Values
Notes
Format
language
units
hardness units
english
metric
mg/L
Summary of Contents for FLECK 5812 XTR
Page 1: ...INSTALLER MANUAL WATER PURIFICATION FLECK 5812 XTR...
Page 18: ...Installer Manual Fleck 5812 XTR Description 18 132 Ref MKT IM 019 E 14 10 2019 3 2 2 Base 4...
Page 108: ...Installer Manual Fleck 5812 XTR Maintenance 108 132 Ref MKT IM 019 E 14 10 2019...
Page 110: ...Installer Manual Fleck 5812 XTR Maintenance 110 132 Ref MKT IM 019 E 14 10 2019...
Page 132: ...www pentairaquaeurope com...