Installer Manual Fleck 5812 - XTR - Operation
Ref. MKT-IM-019 / E - 14.10.2019
99 / 132
8.4. Manual
regeneration
From the home screen, press the regeneration button
to access the regeneration screen.
Press
now
to begin a regeneration immediately, or press
at regen. time
to queue the regeneration for
the programmed regeneration time (2:00 AM default for softeners metered immediate, 12:00 AM
default for filters metered immediate, if day override has not been set). Pressing
regeneration
queued
again will cancel the manual regeneration.
A
During regeneration, press the button
to immediately advance to the next cycle step. Once in
regeneration, the volume or time will be displayed below the button
.
8.5.
Operation during a power failure
The XTR includes internal power backup. In the event of power failure, the controller shifts into a
power-saving mode. The controller stops monitoring water usage. The display and motor shut down,
but it continues to keep track of the time and day for a minimum of eight hours.
The system configuration settings are stored in a non-volatile memory and are stored indefinitely with
or without power. After power outage longer than 8 hours, the time of day button may flash indicating
it needs to be reset. Press the button to stop the time of day from flashing and reset time and day if
needed.
If power fails while the unit is in regeneration, the controller will save the current valve position before
it shuts down. When power is restored, the controller will resume the regeneration cycle from the
point where power failed. If power remains off for more than eight hours, upon power restoration the
regeneration is cancelled, the piston returns to service. The next scheduled regeneration button
flashes and a regeneration is queued at the programmed regeneration time (2:00 AM default for
softeners metered immediate, 12:00 AM default for filters metered immediate, if day override has not
been set).
Caution
If power fails during a regeneration cycle, the valve will remain in its current position until
power is restored. The valve system should include all required safety components to
prevent overflows resulting from a power failure during regeneration.
Regeneration
now
at regen. time
Summary of Contents for FLECK 5812 XTR
Page 1: ...INSTALLER MANUAL WATER PURIFICATION FLECK 5812 XTR...
Page 18: ...Installer Manual Fleck 5812 XTR Description 18 132 Ref MKT IM 019 E 14 10 2019 3 2 2 Base 4...
Page 108: ...Installer Manual Fleck 5812 XTR Maintenance 108 132 Ref MKT IM 019 E 14 10 2019...
Page 110: ...Installer Manual Fleck 5812 XTR Maintenance 110 132 Ref MKT IM 019 E 14 10 2019...
Page 132: ...www pentairaquaeurope com...