IntelliTouch i-Link Protocol Interface Adapter User’s Guide
POOLSP:
Temperature Set Point Control
POOLSP2:
Control/Query Temperature Set Point.
SPASP:
POOLSP is used for the example
Request State:
Query:
#POOLSP ?<cr>
Response:
!00 POOLSP = xx<cr>
(RSPFMT = 0)
!00 xx<cr>
(RSPFMT = 1)
Where xx is the current temperature value (in ASCII) of the pools desired
heating set point.
Set Value:
Command:
#POOLSP = xx<cr>
Where xx is the desired temperature
Response:
!00 POOLSP = xx<cr>
(RSPFMT = 0)
!00 xx<cr>
(RSPFMT = 1)
Where xx is the current temperature value (in ASCII) of the Pools desired
heating set point.
Note:
POOLSP2 is valid only on Models i9+3S and i5S. It is used
to set the High Temperature. It is equivalent. To SPASP.
:
Inc/Dec temperature Set Point
POOLSP-
:
is used for the example
SPASP+:
SPASP-:
Inc/Dec Value:
Command:
#<cr>
Response:
!00 POOLSP = xx<cr>
(RSPFMT = 0)
!00 xx<cr>
(RSPFMT = 1)
Where xx is the current temperature value (in ASCII) of the Pools desired
heating set point.
11