Entering Password
•
When Password Protection is enabled the press of any button other than the speed button will cause
the Screen to ask for a Password.
•
To enter password use the left and right arrows to move the cursor and the
Up
and
Down
arrow
button to scroll through the digit, then press the Enter button to confirm.
Settings: Ramp Speed
The Ramp Speed can be set from 5 RPM to 400 RPM. The default setting is 200 RPM. This means when
the pump changes speeds it will ramp at 200 RPM increments. For example, when the pump changes speeds
from 1500 RPM to 2350 RPM it will ramp to 1700 RPM wait approximately 5 seconds then move to 1900
RPM, wait 5 seconds and then move to 2300 RPM wait five (5) seconds then move to 2350 RPM. This
adjustment is made available to the user to help minimize the occurrence of a false tripping SVRS alarm when
switching speeds.
Note:
Using the five (5) RPM setting would cause the pump to take a long time to
switch between speeds. Using the 400 RPM setting may cause false tripping of the SVRS function when
switching speeds.
To access the Ramp Speed menu:
1. Check that the green power LED is on.
2. Press the
Menu
button. “Settings” is displayed.
3. Press the
Select
button. "Pump Address" is displayed.
4. Use the Up or Down arrow button to scroll to "Ramp Speed".
5. Press the
Select
button. The Default setting is 200 RPM.
6. Press the Left or Right arrow button to move cursor and press up and down arrow to change the
setting.
7. Press
Enter
to save the setting.