background image

Page 10

Pentair Water Commercial Pool and Spa

3A-3. Hi-Limit Checkout

After running the boiler for a long enough period

to bring the water temperature within the range of the
hi-limit, slowly back off the high limit setting until the
unit shuts off. The main burners should re-ignite when
the hi-limit is turned back up to its original setting.

The high limit should now be reset and the boiler

run until it shuts off automatically on high limit.

Now that all tests of the safety shutoff devices

have been completed, refer to Section 3B for the
proper settings of temperature controls.

NOTE:

 Should any of the controls fail to

function properly, consult the factory or your gas
company representative.

3B. To Start Up System

(See Section 3A for Initial Start Up)

Start up boiler:

1.

Be certain system pump is running.

2.

Lighting instructions are provided on the rating
plate and in the User’s Manual and are as
follows:

a.

Turn off main electrical switch.

b.

Turn off all manual gas valves and wait
five minutes.

c.

Set aquastat or thermostat to lowest setting.

d.

Turn manual pilot valve to "ON." For
standing pilot system, press on pilot relay
knob, light pilot and keep relay knob
depressed for one minute then release.
Once the pilot is lit, the power will be
supplied to the gas valve(s) upon activation
of the aquastat.

e.

Slowly turn manual gas valve to "ON."

f.

Reset all safety switches (manual reset high
limit, low water cutoff, etc.).

g.

Turn on main electric switch.

h.

Set temperature controller (aquastat) to
desired temperature. Pilot will light
automatically (intermittent ignition pilot
system) and ignite main burners whenever
the aquastat calls for heat.

i.

Adjust the pool aquastat as follows:

When the pool water has reached the desired

temperature, as measured with an accurate
thermometer, decrease the aquastat setting with a
small screwdriver until the boiler shuts off. The pool
boiler will maintain the existing pool water
temperature automatically.

3C. To Turn Off Boiler

1.

Turn off main electrical switch.

2.

Close all manual gas valves.

3D. Spring and Fall Operation

When the pool is not going to be used for a long

period of time, turn the aquastat down to
approximately 70

o

 F. This will prevent the pool and

surrounding ground from becoming chilled, save on
fuel costs, and also permit the pool water temperature
to be raised back to swimming temperature in a
shorter period of time.

The pool water temperature should not be

maintained below 70

o

 F. Colder water will cause

condensation to form on the heat exchanger when the
boiler does fire. Prolonged operation at a lower
temperature will cause the boiler to foul externally.
See “Improper Use of Boiler.”

3E. Winter Operation

To shut down the boiler for longer periods, turn

both the manual gas valve and pilot gas valve to OFF.
Where the danger of freezing does not exist, the
normal filter cycle should be continued all year long to
circulate water through the system even when the
boiler is turned off or shut down completely.

3E-1. Draining Boiler Before Freezing

If the boiler is located where it will be exposed

to freezing temperatures, it should be drained before
the first frost. Drain the boiler by removing the drain
plug on the bottom of the front header casting. Leave
the plug out until time to use the boiler again. The
boiler must be level for proper drainage. If
compressed air is used to blow out the lines, it is still
necessary to follow the same procedure. Keeping the
pool heated by continuously running the boiler may
not be adequate protection due to the possibility of a
pump or power failure.

3E-2. Improper Use of the Boiler

The Model MT pool boiler is not designed for

continuous use as an anti freezing device for pools.

Operating the boiler at water temperatures below

70

o

 F will cause the heat exchanger fins to be partially

blocked with condensation, resulting in incomplete
combustion. Prolonged operation under these
conditions will result in sooting of the heat exchanger
which can seriously damage the boiler and cause a fire
hazard.

Summary of Contents for MegaTherm MT 2000

Page 1: ...sult causing property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL G...

Page 2: ...it Checkout 10 3B To Start Up System See Section 3A for Initial Start Up 10 3C To Turn Off Boiler 10 3D Spring and Fall Operation 10 3E WinterOperation 10 3E 1 DrainingBoilerBeforeFreezing 10 3E 2 Imp...

Page 3: ...the Pentair Water Commercial Pool and Spa technical support see page 2 or your local representative with any problems or questions regarding this equipment Experience has shown that most operating pr...

Page 4: ...unicating directly through the wall to outside air one within 12 inches of the ceiling the other within 12 inches of the floor Each opening should have a minimum free area of one square inch per 4 000...

Page 5: ...al draft action of the venting system This can create a health hazard by spilling flue products into the boiler room 6 Avoid oversize vent piping or extremely long runs of the pipe which may cause exc...

Page 6: ...essure could be an indication of an undersized gas meter and or obstructed gas supply line 6 The correct burner manifold gas pressure is stamped on the rating plate The regulator is preset at the fact...

Page 7: ...Piping of System to Boiler 1 Be sure to provide gate valves at the inlet and outlet to the boiler so it can be readily isolated for service 2 The pressure relief valve must be installed in the tapped...

Page 8: ...ic flow control valve will maintain proper flow through the boiler regardless of the reduced water flow due to a dirty or clogged filter 2J Automatic Chlorinators A concentration of chlorine in the bo...

Page 9: ...tch on the boiler is in the ON position After placing the manual pilot valves in the open position and resetting all safety devices high limit pressure switch Low Water Cutoff etc pilots can be lit fo...

Page 10: ...pool water temperature automatically 3C To Turn Off Boiler 1 Turn off main electrical switch 2 Close all manual gas valves 3D Spring and Fall Operation When the pool is not going to be used for a lon...

Page 11: ...eriodic Service Inspect the heat exchanger tubes of the Model MT pool boiler on a regular basis In most areas and under most operating conditions the MT pool boiler will operate for years without accu...

Page 12: ...Reassemble in reverse order Be sure to replace the heat exchanger baffles 6 The gas and electric controls installed on the boilers are designed for both dependable operation and long life But the safe...

Page 13: ...is indicated replace coil or operator Boiler is Pounding Knocking or Emitting Steam from Relief Valves Possible Cause What To Do Lower or no water flow This condition is usually caused by lack of adeq...

Page 14: ...and remaining screws from flue collector extension 12 12 Install middle rear panel 13 13 Install front panel making sure opening for removable panel is square 19 14 Install front stiffener 184 2450 an...

Page 15: ...MegaTherm Commercial Pool Heating Boiler Page 15 Figure 12 Outdoor Parts Referenced on page 14...

Page 16: ...sembly 20011301 20011302 20011303 20011304 20011305 20011306 20011307 12 Rear Closure Assembly 20012401 20012402 20012403 20012404 20012405 20012406 20012407 13 Heat Shield Support Bracket 20003201 20...

Page 17: ...MegaTherm Commercial Pool Heating Boiler Page 17 Figure 13 Parts Identification Indoor parts only For tiles see Figure 15...

Page 18: ...20012303 20012304 20012305 20012306 20012307 indoor only 35 Flue End Assembly 20012000 20012000 20012000 20012000 20012000 20012000 20012000 2 2 2 2 2 2 2 36 Upper End Assembly 20011900 20011900 2001...

Page 19: ...shown 2 2 2 2 2 49 b Pilot Relay Standing Pilot W003000 W003000 W003000 W003000 W003000 W003000 W003000 not shown 2 2 2 2 2 50 Pilot Burner Johnson W0034700 W0034700 W0034700 W0034700 W0034700 W00347...

Page 20: ...1 805 553 5000 Trademarks and disclaimers MegaTherm and the Pentair Commercial Pool and Spa logo are trademarks of Pentair Water Pool and Spa Inc Other trade marks and trade names may be used in this...

Reviews: