Pentair Water Commercial Pool and Spa

4.

Liquified petroleum is heavier than air.
Therefore, the pool boiler should not be installed
in pits or other locations where gas could
accumulate. The boiler should be located a safe
distance from LP gas storage and filling
equipment. Consult local codes and fire
protection authorities for advice relative to
specific installation restrictions.

2D. Freeze Protection

Boiler installations are not recommended in areas

where the danger of freezing exists unless proper
precautions are made for freeze protection.

2E. Gas Supply and Piping

Review the following instructions before

proceeding with the installation.

1.

Verify that the boiler is fitted for the proper type
of gas by checking the rating plate. Model MT
boilers are normally equipped to operate below a
2000 foot altitude. Boilers equipped to operate at
higher altitudes have appropriate stickers or tags
attached.

2.

Use the figures in Table 3 to provide adequate
gas piping (check local code for BTU capacity
required).

must be isolated from the gas supply piping
system by closing its individual manual gas
shutoff valve during any pressure testing of the
gas supply piping system at test pressures equal
to or less than 1/2 psig.

5.

Provide gas supply pressure to the boiler as
follows:

Natural

Propane

Min. (inches water column)

7

11

Max. (inches water column)

9

14

Note: The boiler and all other gas appliances

sharing the gas supply line must be firing at maximum
capacity to properly measure the inlet supply pressure.
Low gas pressure could be an indication of an
undersized gas meter and/or obstructed gas supply
line.

6.

The correct burner manifold gas pressure is
stamped on the rating plate. The regulator is
preset at the factory, and normally requires no
further adjustment.

7.

The gas manifold and control assembly was
tested and conforms to the safe lighting and other
performance criteria specified in the latest
editions of ANSI Z21.13 and CGA 3.3 Low
Pressure Boiler Standard.

8.

Before operating the boiler, the complete gas
supply system and all connections must be tested
for leaks using a soap solution. Do not use raw
flame.

Caution

Since some leak test solutions, including soap
and water, may cause corrosion or stress
cracking, the piping must be rinsed with water
after testing, unless it has been determined
that the leak test solution is noncorrosive.

Distance from Gas Meter or

Natural and LP Gas

0-100'

100-200'

200-300'

Indoor

Outdoor

Size

Size

Nat.

LP

Nat.

LP

Nat.

LP

2000

2

3

3

3

2450

2200

3

3

3

3050

2800

3

3

3

3500

3200

3

3

4

4050

3600

3

4

4

4500

4000

3

4

5

4

5000

4500

4

4

5

4

NOTES:
These figures are based on ½" water column pressure drop.
Check supply pressure and local code requirements before
proceeding with work.
Pipe fittings must be considered when determining gas pipe
sizing.

3.

A trap (drip leg) must be provided ahead of the
gas controls (see Figure 5). Where required by
code, provide a second manual gas shutoff valve.
Do not remove manual valve furnished with the
unit.

4.

The boiler and its individual shutoff valve must
be disconnected from the gas supply piping
system during any pressure testing of that system
at test pressures in excess of 1/2 psig. The boiler

Figure 5. Tee Fitting Sediment Trap.

Summary of Contents for MegaTherm MT 2000

Page 1: ...sult causing property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL G...

Page 2: ...it Checkout 10 3B To Start Up System See Section 3A for Initial Start Up 10 3C To Turn Off Boiler 10 3D Spring and Fall Operation 10 3E WinterOperation 10 3E 1 DrainingBoilerBeforeFreezing 10 3E 2 Imp...

Page 3: ...the Pentair Water Commercial Pool and Spa technical support see page 2 or your local representative with any problems or questions regarding this equipment Experience has shown that most operating pr...

Page 4: ...unicating directly through the wall to outside air one within 12 inches of the ceiling the other within 12 inches of the floor Each opening should have a minimum free area of one square inch per 4 000...

Page 5: ...al draft action of the venting system This can create a health hazard by spilling flue products into the boiler room 6 Avoid oversize vent piping or extremely long runs of the pipe which may cause exc...

Page 6: ...essure could be an indication of an undersized gas meter and or obstructed gas supply line 6 The correct burner manifold gas pressure is stamped on the rating plate The regulator is preset at the fact...

Page 7: ...Piping of System to Boiler 1 Be sure to provide gate valves at the inlet and outlet to the boiler so it can be readily isolated for service 2 The pressure relief valve must be installed in the tapped...

Page 8: ...ic flow control valve will maintain proper flow through the boiler regardless of the reduced water flow due to a dirty or clogged filter 2J Automatic Chlorinators A concentration of chlorine in the bo...

Page 9: ...tch on the boiler is in the ON position After placing the manual pilot valves in the open position and resetting all safety devices high limit pressure switch Low Water Cutoff etc pilots can be lit fo...

Page 10: ...pool water temperature automatically 3C To Turn Off Boiler 1 Turn off main electrical switch 2 Close all manual gas valves 3D Spring and Fall Operation When the pool is not going to be used for a lon...

Page 11: ...eriodic Service Inspect the heat exchanger tubes of the Model MT pool boiler on a regular basis In most areas and under most operating conditions the MT pool boiler will operate for years without accu...

Page 12: ...Reassemble in reverse order Be sure to replace the heat exchanger baffles 6 The gas and electric controls installed on the boilers are designed for both dependable operation and long life But the safe...

Page 13: ...is indicated replace coil or operator Boiler is Pounding Knocking or Emitting Steam from Relief Valves Possible Cause What To Do Lower or no water flow This condition is usually caused by lack of adeq...

Page 14: ...and remaining screws from flue collector extension 12 12 Install middle rear panel 13 13 Install front panel making sure opening for removable panel is square 19 14 Install front stiffener 184 2450 an...

Page 15: ...MegaTherm Commercial Pool Heating Boiler Page 15 Figure 12 Outdoor Parts Referenced on page 14...

Page 16: ...sembly 20011301 20011302 20011303 20011304 20011305 20011306 20011307 12 Rear Closure Assembly 20012401 20012402 20012403 20012404 20012405 20012406 20012407 13 Heat Shield Support Bracket 20003201 20...

Page 17: ...MegaTherm Commercial Pool Heating Boiler Page 17 Figure 13 Parts Identification Indoor parts only For tiles see Figure 15...

Page 18: ...20012303 20012304 20012305 20012306 20012307 indoor only 35 Flue End Assembly 20012000 20012000 20012000 20012000 20012000 20012000 20012000 2 2 2 2 2 2 2 36 Upper End Assembly 20011900 20011900 2001...

Page 19: ...shown 2 2 2 2 2 49 b Pilot Relay Standing Pilot W003000 W003000 W003000 W003000 W003000 W003000 W003000 not shown 2 2 2 2 2 50 Pilot Burner Johnson W0034700 W0034700 W0034700 W0034700 W0034700 W00347...

Page 20: ...1 805 553 5000 Trademarks and disclaimers MegaTherm and the Pentair Commercial Pool and Spa logo are trademarks of Pentair Water Pool and Spa Inc Other trade marks and trade names may be used in this...

Reviews: