– maximum Withstand Temperature
is the max. withstand temperature
of the heating cable and the hot-cold joint used, it may also be limited
by the hazardous area approval
– max. sheath Temperature
is the max. sheath temperature of the MI
heating cable based on the application design data
– sheath reference Temperature
is the reference temperature, which
the “max. sheath temperature” calculated in the design of the system
is based upon, (also see “Design Method”)
– power output
refers to the expected power of the heating unit at the
specified voltage/configuration. It is based on the desired maintain
temperature and may be significantly lower than during start-up
phase, in particular for heating cables using conductors with a high
temperature coefficient (e.g. copper conductor). Refer to the design
information for proper saying of the circuit breaker and power supply.
The design calculation must always be in compliance with the
application design and the ambient parameters.
figure 25: Typical mi identification tag (non-hazardous areas)
MI Unit Reference:
B/HSQ1M2500/11.5M/1840/230/0.5M/SC1H2.5/LW/M20/ORD
Heating Cable Ref.:
HSQ1M2500
Element Length:
11.5 m
Year of Manufacture:
2006
Circuit Length (if different):
Grade:
(high)
Nom. Power Output at 230 V: 1840 W @ Maintain Temperature
Order No:
451286
Customer Order No:
Batch number:
XXXXXX
Circuit Reference:
Follow installation and operating instructions.
THIS TAG MUST NOT BE REMOVED
30