60
Table 9 - Continued
Menu or
Sub Menu
Parameter
Unit of Measure
Value
Description
Default
Min
Max
Ex Runtime
Excessive
Runtime
Detection
_
Enabled
Disabled Enabled
Enables or disables Excessive Runtime
Detection.
Excessive
Runtime Hours
Hours
24
1
100
Number of hours Drive can run before it
faults on Excessive Runtime.
Dry Run
Auto Restart
Delay
Minutes
10 Min
3 Min
60 Min
Time Drive waits to restart pump when
Dry Run is detected.
Number of
Resets
–
3
0
5
Number of tries Drive attempts to
restart pump when Dry Run condition is
detected.
Detection Time
M:SS
15 Sec
5 Sec
10 Min
Time the Drive takes to recognize Dry
Run condition.
Sensitivity
PSI
10
0
300
Pressure value that Dry Run condition
is detected at. Dry Run fault will occur
if this pressure cannot be met within
Detection Time window. Lower pressure
= less sensitivity.
Fill Time
M:SS
1 M
15 S
10 M
Time allowed to fill (prime) pipes during
Auto Line Fill process. Relates to Dry
Run Sensitivity value. (Time starts after
55 Hz is reached).
I/O
Digital Input 1
–
Unused
–
–
Selects operation of Drive when
terminal I1 or I2 is used. Select between
Unused, Run Enabled, Ext Fault, and
Setpoint. The Drive will respond to
selected command when voltage is
present at I1 or I2 terminal.
Digital Input 2
Relay Output
–
Unused
–
–
Selects the operation of Drive when
terminal O1 is used. Select between
Unused, Run, and Fault. The Drive
closes the Relay when Run or Fault is
selected.
Over Press
Over Pressure
PSI
80 PSI
15 PSI
97 PSI
Sets Over Pressure Warning value.
Change if higher than 80 PSI system
pressure is needed.
No Ground
No Ground
Detection
–
Enabled
Disabled Enabled
Selects whether Ground Detection
parameter is Enabled or Disabled. If
Disabled is selected, it will revert back
to Enabled after 72 hours. Warning LED
will flash entire time it is Disabled.
Reset
Factory Reset
–
No
No
Yes
Resets all parameters to factory
defaults. Displays Setup Guide after it
is complete. Software version displayed
here. Does not clear fault log.
SW Update
Software Update
–
Disabled Disabled Enabled Used to update software, if necessary.