background image

THERMAL MANAGEMENT SOLUTIONS

EN-RaychemWinterGardH900-IM-H53665      01/13

4 / 12

4 / 12

THERMAL MANAGEMENT SOLUTIONS

6. Install thermal insulation.

• A reliable WinterGard system depends on properly installed and 

weather-proofed thermal insulation.

• Ensure tha

t type and thickness of the insulation are in accordance 

with the information in the heating cable selection tables on 

page 3 and that all pipe work—including valves, joints, wall 

penetrations, and other elements—has been fully  insulated.

• Minimize the potential for mechanical damage to the heating cable 

after instal lation by installing the insulation as soon as you have 

checked the cable installation.

7. Mark the installation.

• Place “Warning” labels for pipe trace applications on the outer 

surface of the insulation at 10-foot intervals (on alternating 

sides of the pipe) to indicate the presence of WinterGard electric 

heating cable. Additional labels and application tape are contained 

in the H903 kit.

8. check the installation

• Prior to powering, check to be sure the heating cable is free of 

mechanical damage (cuts, clamps, etc.).

• Visually check all power connections, end seals, splices, and tees for 

prope

r installation.

• Using a Megohmmeter, test each circuit according to the instructions 

in the “Heating cable testing and maintenance”  section below.

HEATING cAbLE TESTING AND MAINTENANcE

Pentair Thermal Management recommends that the insulation 

resistance between the bus wires and the heater grounding braid 

or metal pipe should be checked during installation using a 2500-

Vdc megohmmeter. Minimum reading should be 1000 megohms, 

regardless of length.
Record the original values for each circuit. Take additional readings 

during regularly scheduled maintenance and compare to the original 

value. If the readings fall below 1000 megohms, inspect cables and 

insulation for signs of damage.

If physical damage is found, the entire damaged section must be 

removed and a new section of heating cable spliced in using only 

approved WinterGard H910 splice kits. Do not repair the damaged 

heating cable section.
If physical damage cannot be found, the complete circuit should be 

removed and replaced with new WinterGard heating cable.

  WARNING: Shock and Fire Hazard. Damaged heating cable 

or components can cause electrical shock, arcing, and fire. 

Do not attempt to energize damaged cable or components. 

Replace them immediately using a new length of heating 

cable and the appropriate WinterGard accessories.

ELEcTRIcAL pROTEcTION

voltage rating
H311, H611, and H612 

110–120 Vac

H621  

208–240 Vac

H622 

208–240 Vac

For the maximum heating cable circuit length permitted for a given 

circuit breaker rating, refer to Table 3. Limit your circuit length based 

on your lowest anticipated start-up temperature.

Ground fault protection:
Pentair Thermal Management and national electrical codes require 

ground-fault equipment protection on each heating cable branch 

circuit. To reduce the risk of fire caused by damage or improper 

installation, circuit breakers such as Square D QO-EPD and QOB-

EPD or equivalent, with a 30-mA trip level, should be used. Alternative 

designs providing comparable levels of ground-fault protection may 

also be acceptable. For technical assistance, call Pentair Thermal 

Management at (800) 545-6258.

Table 3.  Maximum heating cable circuit length on pipe

circuit 

breaker  

rating (A)

Maximum heater length 

(ft) per circuit at start-up 

temperature

Heating cable type

0°F

40°F

WinterGard 120 v 

H311 on pipe

15

150

250

20

200

250

30

250

250

WinterGard plus 120 v 

H611 on pipe

15

125 

150 

20

140

195

30

200

200

WinterGard plus 240 v 

H621 on pipe

15

200

255

20

250

340

30

375

400

WinterGard Wet 120 v 

H612 on pipe

15

125

150

20

140

195

30

200

200

WinterGard Wet 240 v 

H622 on pipe

15

200

255

20

250

340

30

375

400

Note: Maximum circuit lengths are based on start-up load. Steady-state amps 

per foot is dependent upon heating cable temperature.

Table 4.  product data—WinterGard products on pipe only
Heating cable type

WinterGard

WinterGard plus

WinterGard Wet

H311

H611

H621

H612

H622

Service voltage (V)

120

120

240

120

240

Thermal output at 40°F (W/ft)

3

6

6

6

6

Weight per 100 ft (lb)

6

6

6

9

9

Minimum installation temp. (°F)

0

0

0

0

0

Maximum exposure temp. (°F)

150

150

150

150

150

Exposure to chemicals

None

None

None

None

None

Environment

Use only in dry ordinary  

(nonhazardous) areas. 

Use only in dry ordinary  

(nonhazardous) areas.

Use only in wet or dry ordinary 

(nonhazardous) areas.

Summary of Contents for Raychem H900

Page 1: ...ng cable branch circuit Arcing may not be stopped by conventional circuit protection Component approvals and performance are based on the use of specified parts only Do not substitute parts or use vinyl electrical tape The black heating cable core is conductive and can short It must be properly insulated and kept dry Keep components and heating cable ends dry before and during installation Damaged...

Page 2: ...iple trace the pipe using three straight traces at the 11 o clock or 1 o clock position and at the 4 o clock and 8 o clock positions Example 1 Pipe size 1 in Lowest air temp 0 F Insulation thickness 1 2 in Metal pipe WinterGard H311 Plastic pipe WinterGard Plus H611 H621 WinterGard Wet H612 H622 Example 2 Pipe size 2 1 2 in Lowest air temp 20 F Insulation thickness 1 2 in Metal pipe 1 3 WinterGard...

Page 3: ...ating cable can be cut to length without affecting its heat output per foot Protect the heating cable ends from moisture or mechanical damage if they will be left exposed before connection 3 Position and attach heating cable to pipe Be sure all piping to be traced is dry Install heating cable using straight tracing spiraling or multiple tracing according to the Heating cable selection and design s...

Page 4: ...t should be removed and replaced with new WinterGard heating cable WARNING Shock and Fire Hazard Damaged heating cable or components can cause electrical shock arcing and fire Do not attempt to energize damaged cable or components Replace them immediately using a new length of heating cable and the appropriate WinterGard accessories Electrical Protection Voltage rating H311 H611 and H612 110 120 V...

Page 5: ...tant cable tie connect the bottom of each loop to the cable running in the gutter to ensure a drainage channel off the roof and into the gutter and downspout The cable running in the gutter should remain against the bottom of the gutter Extend the top of each heating cable loop beyond where the wall joins the roof Pentair Thermal Management recommends 2 foot clip spacing along the roof edge See th...

Page 6: ... using only approved WinterGard H910 splice kits Do not repair the damaged heating cable section If physical damage cannot be found the complete circuit should be removed and replaced with new WinterGard heating cable WARNING Shock and Fire Hazard Damaged heating cable or components can cause electrical shock arcing and fire Do not attempt to energize damaged cable or components Replace them immed...

Page 7: ...r connection Note De icing and snow melting equipment label must be placed on junction box cover H913 H914 Roof clip H900 Power connection Note De icing and snow melting equipment label must be placed on junction box cove r End seal included in H900 and H910 kits Drip loops Roof without gutters or downspouts Roof with gutters and downspouts Note In all locations route and secure cable to avoid pos...

Page 8: ...outer jacket Cables with no outer jacket look slightly different from those illustrated Open sealing fitting and discard black grommet Slide parts onto cable as shown Push braid back to loosen slightly Gently spread apart braid as shown Bend heating cable and work it through the opening in the braid Lightly score completely around and then down outer jacket Bend heating cable to break jacket at sc...

Page 9: ...mediately pinch with pliers between wires while tube is still hot Hold for 10 seconds to ensure seal Trim braid Crimp ring terminal onto braid Discard black grommet supplied with sealing fitting Slide parts onto heating cable as shown Score between bus wires at base jacket Bend core to break free at base jacket Peel core and any remaining material from bus wires Slip green yellow tube over braid a...

Page 10: ...ed wires Apply Electric De icing label to junction box cover Note For WinterGard Wet cables follow instructions provided with junction box to seal against water if used in wet locations Insert heating cable and tighten fitting as shown Make connections as shown The wire nuts included are not intended for use with aluminum feed wires Note For junction box with clearance hole use lock nut Insert sea...

Page 11: ...avel and remove exposed braid Firmly push end seal onto the cable at least 1 1 2 inches Some gel may ooze out Do not twist or try to remove the end seal during or after insertion Do not reuse an end seal Firmly push end seal onto the cable at least 1 1 2 inches Some gel may ooze out Do not twist or try to remove the end seal during or after insertion Do not reuse an end seal Cleanly cut off the en...

Page 12: ...s of any kind whatsoever whether direct indirect incidental or consequential Notwithstanding the foregoing Pentair Thermal Management shall have no liability whatsoever unless a Buyer promptly notifies Pentair Thermal Management in writing after discovery of an alleged nonconformity and includes a detailed explanation of the alleged nonconformity b Buyer promptly returns the goods to Pentair Therm...

Reviews: