Installation
22
EN-RaychemHWATECOcontroller-IM-H57340 03/13
Building Management System (BMS) (optional)
See Table 5 on page 39.
The BMS input of the HWAT-ECO is a 0 to 10-Vdc
input. If the controller is programmed to have a BMS
connection, the BMS controls the temperature set-
point. Using 300-V rated cable, connect the BMS sig-
nal wire to terminal (PL5). Connect the ground wire
to the “–” and the 0-10 V output to the “+” terminal.
Alarm,
Sensor,
and BMS
terminals
0-10v
ground
BMS
PL3
PL5
PL4
PL6
Alarm c
ont
act
TEMP
BMS
B A
Figure 15: Connecting the BMS