14-Slot AdvancedTCA Shelf
Shelf Installation
11596-100/-101/-102/-103
www.a-tca.com / www.schroff.biz
16
R1.1, July 23, 2008
3.5 Shelf Ground Connection
The Shelf must be properly grounded via the Shelf Ground Terminal.
The location of the Shelf Ground Terminal is shown in
Figure 10: Shelf ground terminal
Torque for Nuts M6: 5.1 Nm (45 in.-lb.)
3.5.1 Specification for the Shelf Ground connection cable
Required wire size:
AWG6
Required terminals:
Use only double lug terminals with 45° angle tongue.
Example for terminal:
PANDUIT
part no.
LCD6-14AH-L
, or
Thomas&Betts
part no.
54205UF
See catalogs at www.panduit.com and www.tnb.com.
Warning!
This Shelf is intended to be grounded. Ensure that the Shelf Ground terminals
are connected to Protective Earth (PE) of the building.
Danger of electrostatic discharge!
Static electricity can harm delicate components inside the Shelf. You must
wear an ESD wrist strap before exchanging any part or electric component!
12706892
1
Shelf Ground Terminal
2
PEM A