Setup

Cooling and heating temperature setpoints are factory set to 95 F/35 C for cooling and 59 

F/15 C for heating.
These setpoints can be changed by adjusting the two dip switches on the printed circuit 

board assembly labeled “Cool” and “Heat”.

Note: The heating function includes a disabled position.

Temperature setpoint dip switch position tables:
Cool

1

2

3

Cooling Set Point 

(°F/°C)

ON

ON

ON

95.0/35.0

(factory set)

ON

ON

OFF

90.5/32.5

ON

OFF

ON

86.0/30.0

ON

OFF

OFF

81.5/27.5

OFF

ON

ON

77.0/25.0

OFF

ON

OFF

72.5/22.5

Heat

1

2

3

Heating Set Point 

(°F/°C)

ON

ON

ON

59.0/15.0

(factory set)

ON

ON

OFF

50.0/10.0

ON

OFF

ON

41.0/5.0

ON

OFF

OFF

32.0/0.0

OFF

ON

ON

23.0/-5.0

OFF

ON

OFF

14.0/-10.0

OFF

OFF

ON

5.0/-15.0

OFF

OFF

OFF

Heating disabled

RSPSupply  -  1-888-532-2706 -  www.RSPSupply.com

http://www.RSPSupply.com/p-6058-Hoffman-TEC24VCNTLR-Thermoelectric-Temperature-Controller-24V.aspx

Summary of Contents for TEC24VCNTLR

Page 1: ...tions Pentair Technical Products 2100 Hoffman Way Anoka MN 55303 1 763 323 8200 1 763 576 3200 www McLeanCoolingTech com INSTRUCTION MANUAL Thermoelectric Temperature Controller TEC24VCNTLR TEC48VCNTL...

Page 2: ...ended wire gauges for wiring Power and earth ground inputs 14 AWG TEC Module and earth ground outputs 14 AWG Fan outputs 20 AWG Alarm outputs 20 AWG Description Source Destination AWG Input Power to C...

Page 3: ...SUPPLIED WIRING CUSTOMER SUPPLIED WIRING THERMISTOR HARNESS INCLUDED WITH CONTROLLER THERMOELECTRIC TEMPERATURE CONTROLLER ALARM OUT EARTH GROUND INPUT POWER WIRE TO TERMINAL 4 FOR THESE UNITS ONLY W...

Page 4: ...sition Temperature setpoint dip switch position tables Cool 1 2 3 Cooling Set Point F C ON ON ON 95 0 35 0 factory set ON ON OFF 90 5 32 5 ON OFF ON 86 0 30 0 ON OFF OFF 81 5 27 5 OFF ON ON 77 0 25 0...

Page 5: ...ode with no power applied to the TEC modules When going from cooling to heating or heating to cooling the control logic provides for a minimum ten minute delay when applying power to the peltier chips...

Page 6: ...in any way or 1 Buyer specified product is inappropriate for system or environment in which it is operating 2 Pentair Technical Products product modified in any way without prior written authorization...

Page 7: ...etermined by Pentair Technical Products not be covered under warranty Buyer will be responsible for all shipping charges and will be billed accordingly H Non warranty repairs are subject to a 75 minim...

Page 8: ...Protecting Electronics Exceeding Expectations Pentair Technical Products 2100 Hoffman Way Anoka MN 55303 1 763 323 8200 1 763 576 3200 www McLeanCoolingTech com RSPSupply 1 888 532 2706 www RSPSupply...

Reviews: