Teel Operating Instructions and Parts Manual
4RJ93, 4RJ94 and 4RJ95
Teel Pool Pump With Integral Trap
®
E
N
G
L
I
S
H
Electrical (Continued)
VOLTAGE
Voltage at motor must be not more
than 10% above or below motor
nameplate rated voltage or motor may
overheat, causing overload tripping
and reduced component life. If voltage
is less than 90% or more than 110% of
rated voltage when motor is running
at full load, consult power company.
GROUNDING/BONDING
Install, ground, bond, and wire motor
according to local or National Electrical
Code requirements.
Permanently ground motor. Use green
ground terminal provided under
motor canopy or access plate (See Fig.
2); use size and type wire required by
code. Connect motor ground terminal
to electrical service ground.
Bond motor to pool structure. Use a
solid copper conductor, size No. 8
AWG (8.4 sq.mm) or larger. Run wire
from external bonding lug (See Fig. 2)
to reinforcing rod or mesh.
Connect a No. 8 AWG (8.4 sq.mm) solid
copper bonding wire to the pressure
wire connector provided on the motor
housing and to all metal parts of the
swimming pool, spa, or hot tub and to
all electrical equipment, metal piping
or conduit within 5 feet (1.5 m) of the
inside walls of swimming pool, spa, or
hot tub.
WIRING
Pump must be permanently connected
to circuit. The Wiring Chart below
gives correct wire and circuit breaker
sizes for the pump alone. If other
lights or appliances are also on the
same circuit, be sure to add their amp
loads to pump amp load before
figuring wire and circuit breaker sizes
(If unsure how to do this or if this is
confusing, consult a licensed
electrician). Use the load circuit
breaker as the master on-off switch.
AWG WIRE SIZE
1
115/230/1
15.3/7.6
20/15
12/14
8/14
6/14
6/12
4/10
1
1
/
2
115/230/1
19.2/9.6
25/15
10/14
8/14
6/12
4/10
4/10
2
230/1
12.0
20
14
14
12
10
10
WIRING CHART – RECOMMENDED WIRE AND FUSE SIZES
Max. Load
Branch Fuse*
Distance in Feet from Motor to Supply
Motor HP
Volts/Ph
Amp
Rating Amps†
0 - 100
101 - 200
201 - 300
301 - 400
401 - 500
(*) Fusetrons are recommended instead of fuses on all motor circuits
(†) At 115/230V
Figure 2 – Typical ground screw and
bonding lug locations.
Figure 3 – Wiring hook-up diagram
Bonding
Lug
Green
Ground
Screw
White
230
Volt
Lines
A
B
L2
L1
Blue
SINGLE
VOLTAGE
MOTORS
DUAL
VOLTAGE
MOTORS
A
B
L2
L1
White
w/Black
Tracer
Black
115
Volt
Lines
A
B
L2
L1
White
w/Black
Tracer
Black
230
Volt
Lines
Motor Terminal Board Connections
WARNING
Hazardous voltage.
Can shock, burn, or
cause death.
Disconnect power to motor
before working on pump or
motor.
Ground motor before
connecting to power supply.