background image

EN-TraceTekTT1100OHP-IM-H58263      01/15

THERMAL BUILDING & 

INDUSTRIAL HEAT TRACING SOLUTIONS

3 / 8

Maximum

offset = 1/4 in

End termination

Cable connector with pins

toward alarm module

Tie-wrap

Sensor

cable

TraceTek

Systems

Service

loop

4

connect, orient, install, and test each length of sensing cable in 

sequence

1. 

connect

 a Modular End Termination (TT-MET-PC) to the first sensing-cable 

length to be installed.

2. 

orient

 sensing cable so the connector used with the end termination will 

be the furthest away from connection to the TraceTek alarm module. Work 

out from the alarm module connection. For sensing cable on reels (lengths 

over 10 feet (3 m)), put the reel on an axle and pull the cable out.

3. 

install

 sensing cable in accordance with the leak detection layout plan.

A. For pipeline applications:

•  Position the cable along the bottom of the pipe and use tie wraps to 

secure the cable at the 6 o’clock position. Maintain cable position 

within 1/4 inch (6 mm) of 6 o'clock position.

•  Tie wraps should be long enough to go around the pipe and the sen-

sor cable.

•  Use one tie wrap every 12 in to 18 in (300 to 450 mm) along the pipe 

with extra tie wraps at fittings or bends as needed.

important

: It is the installer’s responsibility to position the sensor cable 

correctly. The cable must trace the lowest point of the pipe or fittings 

such that any water leaking from the pipe or fittings will drip onto the 

cable surface as it drips off the bottom of the pipe or fitting. Do not 

install the cable on the top or side surface of a pipe. Do not spiral the 

cable on horizontal pipe.

exception

: If the cable is used to trace vertical pipe, the cable should be 

spiraled around the pipe and secured with tie-wraps.

B. For sumps, containment trenches, and subfloor applications:

•  Pull the cable alongside the installed hold-down clips; minimum bend 

radius is 2 in (50 mm). Leave 6 in (150 mm) of sensing cable on each end 

for the connector service loop.

important

: Verify that the adhesive securing the hold-down clips has 

dried; liquid adhesive must not contact the cable.
Push sensing cable into the hold-down clips and position the sensing 

cable to lay flat on the surface to be monitored. Secure by snapping 

hold-down clip end into base.

4. 

test

 each length of sensing cable after installing it and before attaching 

it to cable already installed. Confirm that the sensing cable is clean and 

intact by following the Sensing Cable Test Procedure.

5. 

connect

 the sensing cable to the cable string (lengths of sensing cable 

connected in series) previously installed.
For sumps, containment trenches, and subfloor applications:
•  Leave a service loop at each connector as shown.
•  Mark the connector position on the layout plan.
•  Install TraceTek mapping tag (TT-TAG).
• 

note

: As an extra precaution on large installations, periodically test the 

entire cable string to confirm that all installed sensing cable is still clean 

and intact.

•  Unplug the end termination and connect it to the next length of sensing 

cable to be installed.

6. 

repeat

 the installation sequence for each length of cable.

Summary of Contents for TraceTek TT1100-OHP

Page 1: ...esigned for testing and troubleshooting TraceTek systems Digital multimeter Can be used as an alternative or supplement to the PTB Meter must have 20 MΩ range TT MAPPING CAP PC PN P000000872 Used to simulate leaks at connector points during commissioning and mapping process Extra TT MLC PC PN 683262 000 Leader cable Used with the ohmmeter to make easier connections to the sensor cable for resistan...

Page 2: ...here hold down clips will be placed so adhesive can work properly Position hold down clips so the sensing cable will provide the desired leak detection coverage To best secure the cable alternate the direction of the hold down clips and install them at intervals of no greater than 6 feet 2 m and at every change in direction at sides of trench for example Important Let the adhesive dry per manufact...

Page 3: ...ps off the bottom of the pipe or fitting Do not install the cable on the top or side surface of a pipe Do not spiral the cable on horizontal pipe Exception If the cable is used to trace vertical pipe the cable should be spiraled around the pipe and secured with tie wraps B For sumps containment trenches and subfloor applications Pull the cable alongside the installed hold down clips minimum bend r...

Page 4: ...ing Cable Test Procedure 3 Connect the sensing circuit to the TraceTek alarm module and activate the system as soon as is practical Use the alarm module to monitor the sensing cable during the final stages of construction Take precautions if installation is incomplete at end of work day At the end of the work day Ensure that there are no open connectors Each sensing cable should be connected to a ...

Page 5: ...A use the PTB to locate the liquid or contamination and take appropriate corrective action Method with Ohmmeter 1 Ensure the end termination is connected to the sensing cable If checking several lengths of sensing cable in series a cable string ensure they are all connected 2 Connect a Modular Leader Cable TT MLC PC to the sensing cable 3 Verify that the sensing cable is intact Loop 1 Measure the ...

Page 6: ...e to have TT MBCs installed on branches as needed to fully trace a pipe system D Install an end termination TT MET PC at the end of the main line and each branch line Note A good check on the system design and bill of materials is that the total number of end terminations installed in the system should equal the number of branch connectors plus one E Optional Install jumper cables TT MJC xxx PC as...

Page 7: ...a channel number and display the words SYSTEM NORMAL If the Yellow LED is on in any of these instruments or the words Cable Break or Loop Break is displayed then the cable system must be inspected for loose connections missing end terminations until the cable continuity is established and the Normal condition is achieved LEAK testing can be done with a mapping cap TT MAPPING CAP PC The MAPPING CAP...

Page 8: ...uced for a new leak Yellow LED visible on TTC 1 TTSIM 1A TTSIM 2 or flashing yellow LED on TTSIM 1 Could be cable break or service indication Refer to alarm module instructions for more infor mation For Cable break indication Check for loose connectors missing end terminations broken jumper wires or physical dam age to the cable Repair or replace cable if necessary The TT MET PC end termination ca...

Reviews: