BARCON LHC/PPC
Operation of devices with displays
Subject to reasonable modifications due to technical advances.
Copyright Fuchs, Printed in Germany
Fuchs Group • Tel.: Germany (06 21) 7 76-0 • USA (330) 4 25 35 55 • Singapore 7 79 90 91 • Internet http://www.pepperl-fuchs.com
D
a
te
of
I
s
s
u
e
1
5.
1
2
.2000
37
Example:
Level 100 %:
4000 mm
Density:
1 g/cm
3
Densitiy correction:
0.9 g/cm
3
Span end point:
The span (end-point) must be re-calibrated (with or without pressure) to 4000 mm in
order to prevent a 4000 mm level tank from being overfilled.
Please check the following if "Wrong Entry" appears in the Evaluation
menu:
• Whether or not more than 32 value pairs are entered in the table for
tank linearization (please note: P 0 and P 31 are fixed at 0 % and
100 % respectively)
• Whether or not an existing height value was tried to be stored again.
Please enter correct values.
A change or correction in the density causes a change in the span end-
point’s unit of measure (mm, m, inch, feet). The span end-point must be
re-calibrated when changing the medium to be measured (due to a
change in density).
4000 mm
•
1 g/cm³
0.9 g/cm³
= 4444 mm
Important