27
Conducted EMC Tests
Immunity
6.3
Referenced Documents
■
Manual: "Using Fuchs Fieldbus Equipment in Zone 2 Hazardous Area
Environment"
■
PROFIBUS & PROFINET International (PI): PROFIBUS PA Installation Guideline.
■
Manual: System Description K-System.
Standard
Type
Test
Level
Category
EN 61000-4-2
Electrostatic discharge, direct contact
6 kV
A
Electrostatic discharge, indirect, air
8 kV
A
EN 61000-4-3
Electromagnetic field radiated, radio
frequency
10 V/m
A
EN 61000-4-4
Fast transients burst on signal lines
1 kV
A
Fast transients burst on power lines
2 kV
A
EN 61000-4-5
Slow transient surge on signal lines
1 kV
B
Slow transient surge on shielded lines
2 kV
B
EN 61000-4-6
Conducted immunity, radio frequency
10 V
A
EN 55011
Reduction factor conducted emission
Class A
_
Reduction factor radiated emission
Class A