Safety Function
The device transfers analog signals from the input to the output with a tolerance of 2 % related
to the full signal range.
Use the following DIP switch settings for safety-relevant applications:
DIP Switch Settings KCD2-STC-(Ex)1(.SP)(-Y1)
DIP Switch Settings HiC2025(Y1)
Safe State
In the safe state, the following values must be reached at the output:
•
< 3.6 mA or > 21.5 mA,
•
< 0.9 V or > 5.375 V,
Reaction Time
The reaction time for all safety functions is < 20 ms.
Function
S1
S2
S3
S4
Current source 4 mA to 20 mA
II
II
I
II
Voltage source 1 V to 5 V
II
II
I
I
Current sink 4 mA to 20 mA
II
I
II
II
Table 3.1
Function
S1
S2
S3
S4
Current source 4 mA to 20 mA
OFF
OFF
ON
OFF
Voltage source 1 V to 5 V
OFF
OFF
ON
ON
Current sink 4 mA to 20 mA
OFF
ON
OFF
OFF
Table 3.2
Note!