2
018-
08
8
Functional Safety KCD2-STC-(Ex)1(.SP)(-Y1), HiC2025(Y1)
Product Description
KCD2-STC-Ex1-Y1
This isolated barrier is used for intrinsic safety applications.
The device supplies 2-wire transmitters in the hazardous area.
The device transfers the analog input signal to the non-hazardous area as an isolated current
value.
Bi-directional communication is supported for SMART transmitters that use current modulation
to transmit data and voltage modulation to receive data.
If the HART communication resistance in the loop is too low, the internal resistance
can be used.
Test sockets for the connection of HART communicators are integrated into the terminals
of the device.
The output is selected as a current source, current sink, or voltage source via DIP switches.
The device is mounted on a 35 mm DIN mounting rail according to EN 60715.
HiC2025
This isolated barrier is used for intrinsic safety applications.
The device supplies 2-wire transmitters in the hazardous area, and can also be used
with current sources.
The device transfers the analog input signal to the non-hazardous area as an isolated
current value.
Bi-directional communication is supported for SMART transmitters that use current modulation
to transmit data and voltage modulation to receive data.
The output is selected as a current source, current sink, or voltage source via DIP switches.
This device mounts on a HiC termination board.
HiC2025Y1
This isolated barrier is used for intrinsic safety applications.
The device supplies 2-wire transmitters in the hazardous area.
The device transfers the analog input signal to the non-hazardous area as an isolated
current value.
Bi-directional communication is supported for SMART transmitters that use current modulation
to transmit data and voltage modulation to receive data.
The output is selected as a current source, current sink, or voltage source via DIP switches.
This device mounts on a HiC termination board.