Functional Safety KFD2-RSH-1.2E.L*(-Y1)
Operation
2
01
9-
12
19
Proof Test Procedure
1.
Enable the internal fault detection and the line fault detection. See chapter 4.2.1.
2.
Check the device as shown in the following tables.
3.
After check reset the device to the necessary settings.
4.
Check the correct behavior of the safety loop. Is the configuration correct?
Only if all tests are successfully done, the proof test is successful.
Test No.
Input
Output
1
V = 0 V DC between terminals 7+ and 8-
2
Wait at least 2 seconds.
•
LED OUT is off.
•
LED FLT is off
1
.
3
V = 24 V DC between terminals 7+ and 8-
4
Wait at least 2 seconds.
•
LED OUT is on.
•
LED FLT is off
1
.
5
V = 0 V DC between terminals 7+ and 8-
6
Wait at least 2 seconds.
•
LED OUT is off.
•
LED FLT is off
1
.
7
V = 24 V DC between terminals 7+ and 8-
8
Wait at least 2 seconds.
•
LED OUT is on.
•
LED FLT is off
1
.
9
V = 0 V DC between terminals 7+ and 8-
10
Wait at least 2 seconds.
•
LED OUT is off.
•
LED FLT is off
1
.
11
V = 24 V DC between terminals 7+ and 8-
12
Wait at least 2 seconds.
•
LED OUT is on.
•
LED FLT is off
1
.
Table 5.2 Expected test results for the proof test
1
When the FLT LED flashes, a line fault is present. Check whether the supply voltage and the connected load are in the OK area
of the line fault detection.
When the FLT LED is lit continuously, an internal fault is present. Reset the internal fault by interrupting the power supply
(terminals 14+/15-).