Leakage Current Measurement
Resistance Measurement
Device
Step
Measurement
Expected result
M-LB-2112(.SP)
1
1 V between terminals 4 and 5
1 V between terminals 5 and 4
Leakage current below 5
A
M-LB-Ex-2114(.SP)
1
2
3
1 V between terminals 4 and 5
1 V between terminals 5 and 4
1 V between terminal 4 and ground
1 V between terminal 5 and ground
Leakage current below 10
A
M-LB-2142(.SP)
1
30 V between terminals 4 and 5
30 V between terminals 5 and 4
Leakage current below 3
A
M-LB-Ex-2144 (.SP)
1
2
3
30 V between terminals 4 and 5
30 V between terminals 5 and 4
30 V between terminal 4 and ground
30 V between terminal 5 and ground
Leakage current below 6
A
Table 5.1
Device
Step
Measurement
Expected result
M-LB-21*2(.SP)
1
Resistance between terminals 2 and 5
Resistance below 3.0
M-LB-Ex-21*4(.SP)
1
2
Resistance between terminals 2 and 5
Resistance between terminals 3 and 4
Resistance below 3.0
Table 5.2