Functional Safety M-LB-(Ex-)5000-System
Operation
201
8-03
17
Leakage Current Measurement
Resistance Measurement
Device
Step
no.
Measurement
Expected result
M-LB-(Ex-)5*42
1
30 V between terminals 3 and 4
Leakage current below 3
A
M-LB-(Ex-)5*44
1
2
3
30 V between terminals 3 and 4
30 V between terminal 3 and ground
30 V between terminal 4 and ground
Leakage current below 6
A
M-LB-(Ex-)5*12
1
1 V between terminals 3 and 4
Leakage current below 5
A
M-LB-(Ex-)5*14
1
2
3
1 V between terminals 3 and 4
1 V between terminal 3 and ground
1 V between terminal 4 and ground
Leakage current below 5
A
M-LB-(Ex-)5*41
1
15 V between terminals 3 and 4
Leakage current below 3
A
M-LB-(Ex-)5*43
1
2
15 V between terminals 3 and 4
15 V between terminal 3 and ground
Leakage current below 6
A
M-LB-(Ex-)5*11
1
1 V between terminals 3(+) and 4(-)
Leakage current below 5
A
M-LB-(Ex-)5*13
1
2
1 V between terminals 3(+) and 4(-)
1 V between terminal 3(+) and ground(-)
Leakage current below 5
A
Table 5.1
Device
Step
no.
Measurement
Expected result
M-LB-(Ex-)5**1
M-LB-(Ex-)5**2
1
Resistance between terminals 1 and 4
Resistance below 0.5
M-LB-(Ex-)5**3
M-LB-(Ex-)5**4
1
2
Resistance between terminals 1 and 4
Resistance between terminals 2 and 3
Resistance below 0.5
Table 5.2