Commissioning
6
Commissioning
6.1
Programming the Switching Outputs
2 switching windows with a window width of 5
°
(+/- 2.5
°
) are preset at the factory. The switching
windows lie between the angle settings 117.5
°
... 122.5
°
(S1), and 237.5
°
... 242.5
°
(S2). You
can modify the position and width of these switching windows by programming them accord
-
ingly. The start and end points of a switching window can be defined at any desired position.
The smallest angle range of a switching window can be 5
°
and the largest angle range can be
360
°
.
To ensure reliable switching characteristics, each switching output has a switching hysteresis
of 1
°
when switched off, which prevents the electrical output signal from wavering.
The switching hysteresis is located at the top or bottom end of the switching window, depend
-
ing on the direction of rotation of the actuator element. The following graphic illustrates the
switching characteristics in principle, using the example of the sensor at switching output S1.
Figure 6.1
Program switching output 1 (S1) as follows:
Programming switching output S1
1.
Make sure that the sensor is mounted correctly and securely, and check that an actuator with
the specified dimensions is positioned at the correct distance from the surface of the sensor.
See chapter 5.2
2.
Unlock the keyboard, if locked.
3.
Press the S1 button for
2 s.
The flashing yellow LED indicates that the device is ready for you to teach in the switching
window start point.
S11
S12 S12+H
H
S11-H
S12
H
S11
Signal at switching output
Angle position
Direction of rotation
actuator
Angle position
Note
Unlocking the buttons
If the keylock is active, it must first be deactivated. The sensor indicates that the keylock is
active by changing the color of the "Power/Error" LED to red when a button is pressed. To
unlock the buttons, press and hold the S1 and S2 buttons simultaneously for 3 seconds. The
color of the "Power/Error" LED changes to green. The buttons are no longer locked.