Power Supply PS1000-A6-48.5
EMC
20
21
-1
1
25
17
EMC
The power supply is suitable for applications in industrial environment as well as in residential,
commercial and light industry environments.
EMC Immunity
According to generic standards: EN 61000-6-1 and EN 61000-6-2
Electrostatic discharge
EN 61000-4-2
Contact discharge
Air discharge
8kV
15kV
Criterion A
Criterion A
Electromagnetic RF field
EN 61000-4-3
80MHz-2.7GHz
20V/m
Criterion A
Fast transients (Burst)
EN 61000-4-4
Input lines
Output lines
DC-OK signal (coupling
clamp)
4kV
2kV
2kV
Criterion A
Criterion A
Criterion A
Surge voltage on input
EN 61000-4-5
L
→
N
L
→
PE, N
→
PE
2kV
4kV
Criterion A
Criterion A
Surge voltage on output
EN 61000-4-5
+
→
–
+ / –
→
PE
1kV
2kV
Criterion A
Criterion A
Surge voltage on signals
EN 61000-4-5
DC-OK signal
→
PE
1kV
Criterion A
Conducted disturbance
EN 61000-4-6
0.15-80MHz
20V
Criterion A
Mains voltage dips
EN 61000-4-11 0% of 100Vac
40% of 100Vac
70% of 100Vac
0% of 200Vac
40% of 200Vac
70% of 200Vac
0Vac, 20ms
40Vac, 200ms
70Vac, 500ms
0Vac, 20ms
80Vac, 200ms
140Vac, 500ms
Criterion A
Criterion C
Criterion C
Criterion A
Criterion A
Criterion A
Voltage interruptions
EN 61000-4-11 0% of 200Vac (=0V)
5000ms
Criterion C
Voltage sags
SEMI F47 0706 Dips on the input voltage according to SEMI F47 standard
80% of 120Vac (96Vac)
70% of 120 Vac (84Vac)
50% of 120 Vac (60Vac)
1000ms
500ms
200ms
Criterion A
Criterion A
Criterion A
Powerful transients
VDE 0160
Over entire load range
750V, 0.3ms
Criterion A
Criterion A
The device shows normal operation behavior within the defined limits.
Criterion C
Temporary loss of function is possible. Power supply may shut-down and restarts by itself.
No damage or hazards for the power supply will occur.
EMC Emission
According to generic standards: EN 61000-6-3 and EN 61000-6-4
Conducted emission
input lines
EN 55011, EN 55015, EN 55022,
FCC Part 15, CISPR 11,
CISPR 22
Class B
Conducted emission
output lines
1
IEC/CISPR 16-1-2,
IEC/CISPR 16-2-1
Limits for DC power port according
EN 61000-6-3 fulfilled
Radiated emission
EN 55011, EN 55022
Class B
Harmonic input current
EN 61000-3-2
Class A fulfilled between 0A and 6A load
Class C fulfilled between 2.5A and 6A load
Voltage fluctuations, flicker EN 61000-3-3
Fulfilled
2
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2)
this device must accept any interference received, including interference that may cause undesired operation.
1
For information only, not mandatory for EN 61000-6-3.
2
Tested with constant current loads, non pulsing.