Power Supply PS1000-A6-48.5
Environment
20
21
-1
1
27
18
Environment
Figure 18.1 Output current vs. ambient temp.
Operational temperature
1
-25°C to +70°C (-13°F to 158°F)
Reduce output power according to
Storage temperature
-40°C to +85°C (-40°F to 185°F)
For storage and transportation
Output de-rating
1.9W/°C
6.5W/°C
B45°C and +60°C (113°F to 140°F)
B60°C and +70°C (140°F to 158°F)
Humidity
5 to 95% r.h.
According to IEC 60068-2-30
Do not energize while condensation is
present
Vibration sinusoidal
2
2-17.8Hz: ±1.6mm; 17.8-500Hz:
2g
2 hours / axis
According to IEC 60068-2-6
Shock
2)
30g 6ms, 20g 11ms
3 bumps / direction, 18 bumps in
total
According to IEC 60068-2-27
Altitude
0 to 2 000m (0 to 6 560ft)
Without any restrictions
2 000 to 6 000m
(6 560 to 20 000ft)
Reduce output power or ambient
temperature, see Figure 18.2.
Altitude de-rating
13.5W/1 000m or 5°C/1 000m
Above 2 000m (6 560ft), see Figure 18.2
Over-voltage category
III
According to IEC 62477-1 for altitudes
up to 2000m
II
According to IEC 62477-1 for altitudes
from 2 000m to 6 000m
Degree of pollution
2
According to IEC 62477-1, not conductive
LABS compatibility
The unit does not release any silicone or other LABS-critical substances and
is suitable for use in paint shops.
Corrosive gases
ISA-71.04-1985, Severity Level G3, IEC 60068-2-60 Test Ke Method 4
Audible noise
Some audible noise may be emitted from the power supply during no load,
overload or short circuit.
1
Operational temperature is the same as the ambient or surrounding temperature and is defined as the air temperature 2cm below
the unit.
2
Tested in combination with DIN mounting rails according to EN 60715 with a height of 15mm and a thickness of 1.3mm and standard
orientation.
Allowed Output Current at 48V
0
-25
0
20
40
70°C
1A
2A
3A
4A
5A
6A
60
A
Ambient Temperature
A...90 to 264Vac, continuous
B... short term
B