Power Supply PS1000-A6-48.5
Safety Features
20
Safety Features
Input / output separation
Double or reinforced galvanic isolation
SELV
IEC/EN 60950-1
PELV
IEC/EN 60204-1, EN 62477-1, IEC 60364-4-41
Class of protection
I
PE (Protective Earth) connection required
Isolation resistance
> 500MOhm
At delivered condition between input and output,
measured with 500Vdc
> 500MOhm
At delivered condition between input and PE,
measured with 500Vdc
> 500MOhm
At delivered condition between output and PE,
measured with 500Vdc
> 500MOhm
At delivered condition between output and DC-
OK contacts, measured with 500Vdc
PE resistance
< 0.1Ohm
Resistance between PE terminal and the housing
in the area of the DIN-rail mounting bracket.
Touch current (leakage current) Typ. 0.14mA / 0.36mA
At 100Vac, 50Hz, TN-,TT-mains / IT-mains
Typ. 0.20mA / 0.50mA
At 120Vac, 60Hz, TN-,TT-mains / IT-mains
Typ. 0.33mA / 0.86mA
At 230Vac, 50Hz, TN-,TT-mains / IT-mains
Max. 0.18mA / 0.43mA
At 110Vac, 50Hz, TN-,TT-mains / IT-mains
Max. 0.26mA / 0.61mA
At 132Vac, 60Hz, TN-,TT-mains / IT-mains
Max. 0.44mA / 1.05mA
At 264Vac, 50Hz, TN-,TT-mains / IT-mains