Commissioning
2
01
7-
11
19
4.2.2
External Parameterization Using Code Cards
During external parameterization, the reader scans special code cards optically and configures
the relevant parameters. Simply hold the corresponding code cards at the correct distance in
front of the lens on the reader. The standard code cards are contained in the appendix.
The following parameters can be configured using code cards:
Output code [binary, gray]
Reading head resolution [0.1 mm, 1 mm, 10 mm]
Trigger source [auto, hardware]
Function of the input/output 2 [as input: None, trigger input/as output: None, overspeed,
warning, error, dirt, event, no position]
Function of input/output 3 [as input: none, trigger input/as output: none, overspeed,
warning, error, dirt, event, no position]
Activating the Programming Mode
The switchover from normal mode to parameterization mode is made by pressing button 2 on
the back of the reader.
Activating parameterization mode
1. Press button 2 for longer than 2 seconds.
This will cause yellow LED3 to flash.
2. Hold the "ENABLE" code in front of the camera system on the reader to trigger final
activation
If the "ENABLE" activation code is detected, the green LED2 lights up for 1 second. If
the activation code is not detected, LED2 lights up red for 2 seconds.
Carrying out parameterization
Place the parameterization code in the field of vision of the camera module.
After the parameterization code is detected, the green LED2 lights up for 1 second. In the
event of an invalid parameterization code, LED2 lights up red for 2 seconds.
Exiting parameterization mode
Hold the "STORE" code in front of the camera system on the reader to save the configuration
When the "STORE" memory code is detected, the green LED2 lights up for 1 second. The
parameterization is stored in the nonvolatile memory of the reader and parameterization mode
is terminated. Parameterization of the reader is now complete. If the memory code is not
detected, LED2 lights up red for 2 seconds.
Note!
External parameterization of the reader using code cards must be started within 10 minutes of
the reader switching on. A time lock disables the reader once this time has elapsed. The time
lock remains inactive during the parameterization process. The time lock disables the reader
only if no parameterization activities take place for more than 10 minutes.
If a button is pressed when the time lock is enabled, all LEDs flash and remain lit for two
seconds during each flashing cycle.
Note!
Tap button 2 to exit parameterization mode. Any parameter changes that are made but have
not yet been saved are discarded. The reader operates with the last valid parameters that were
saved.