VBA-2E-G11-I/U/PT100-*
Commissioning
2014-
02
15
Parameter P2: Peripheral Fault
Default value P2=1, active
Parameter P2 is used to switch notification of a peripheral fault in the event of a measuring
overrange on or off (see chapter 9). If notifications are activated, the AS-i/FAULT LED flashes in
the event of a peripheral fault, and a notification is sent to the master.
A peripheral fault is always reported if:
■
The power supply is overloaded.
■
The external power supply is not available when the INT/EXT switch = EXT.
Parameter P3: Current Input 0 mA ... 20 mA
Default value P3=1, not active
Parameter P3=0 is used to set both input channels to current mode. Wire break detection is
simultaneously deactivated. (see chapter 9.1)