T
В
-01 Electromechanical box tripod turnstile with two built-in readers
11
Detector and Alarm relays is indicated by lighting/going out of red indi-
cators located near the corresponding relays (Fig. 3). The output cas-
cades for “PASS A”, “PASS B”, “Ready”, “Det Out” and “Alarm” are the
relay contacts with the following signal characteristics (Ref. Fig. 5):
maximum
commutation voltage .................................. 42V DC;
maximum switched current ...........................................0.25
А
;
closed
contact
resistance .................. no more than 0.15Ohm.
Figure 5 – Output cascades for PASS A, PASS B, Ready, Det Out and Alarm
6.5. Control modes
6.5.1 There are two modes of the turnstile control - a pulse control mode and a
potential control mode. They determine available operating modes of the
turnstile (Table 3 and Table 4).
6.5.2 The control mode is set by the jumper on a J1 connector (the J1 connector
location is shown in Figure 3: the jumper is installed – the pulse control
mode, the jumper is not installed – the potential control mode). The jumper
is installed at delivery.
6.5.3 At both control modes the turnstile is controlled by input of a control signal.
Passage waiting time in the pulse control mode is 5 seconds regardless of
duration of the control signal (impulse). In the potential control mode
passage waiting time equals duration of the control signal.
Summary of Contents for Turnichetul TB 1
Page 37: ...www percoweb com...