19
103092
IMPORTANT:
Hold pressure regulator with wrench when connecting it to gas piping
and/or fittings.
PRESSURE TESTING GAS SUPPLY PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
1. Disconnect heater and its individual manual shutoff valve from gas supply
piping system. Pressures in excess of 1/2 psig will damage heater regulator.
2. Cap off open end of gas pipe where manual shutoff valve was connected.
3. Pressurize supply piping system by either using compressed air or
opening main gas valve located on or near gas meter.
Continued
Tee Joint
Reducer
Bushing to
1/8" NPT
1/8" NPT
Plug Tap
Test
Gauge
Connection *
Tee Joint
Pipe
Nipple
Cap
Sediment
Trap
Pressure
Regulator
1/2" NPT
Pipe Nipple
Ground
Union
Joint
Heater
Cabinet
3" Minimum
Note:
Burner bracket
not shown for clarity
Manual Shutoff Valve *
From Gas Meter
(4" W.C. to 10.5" W.C. Pressure)
CONNECTING
TO GAS
SUPPLY
Continued
CHECKING
GAS
CONNECTIONS
Figure 20 - Gas Connection
* An A.G.A. design-certified manual shutoff valve with 1/8" NPT tap is an accept-
able alternative to test gauge connection.
WARNING ICON
G 001
WARNING
Test all gas piping and connections for leaks after installing or
servicing. Correct all leaks at once.
WARNING ICON
G 001
WARNING
Never use an open flame to check for a leak. Apply a mixture of
liquid soap and water to all joints. Bubbles forming show a leak.
Correct all leaks at once.