5-9
Basic Configuration
•
Web Protection:
Enables/Disables and configures the Invalid Access function for Web
connections. When this item is enabled and excessive Invalid Access Attempts via Web
are detected, then the RPS will lock out the offending MAC address for the user-defined
Web Lockout Duration Period or until the /UL command is issued. Note that for Web
protection, the lockout trigger is a function of the Web Hit Count parameter and the Web
Lockout Duration Parameter.
•
Lockout Enable:
Enables/Disables Invalid Access Lockout protection for web
connections. (Default = Off.)
•
Web Hit Count:
The number of invalid attempts that must occur during the length
of time specified by the Web Lockout Duration period in order to trigger the Invalid
Access Lockout feature for Web access. For example, if the Web Hit Count parameter
is set to 10 and the Web Lockout Duration parameter is set to 30 minutes, then the
RPS will lock out the offending MAC address for 30 minutes when over 10 invalid
access attempts occur during any 30 minute long period. (Default = 20.)
•
Web Lockout Duration:
This option selects both the length of time that a Web
Lockout will remain in effect and also the time period over which invalid access
attempts will be counted. When a Web Lockout occurs, the offending MAC address
will be prevented from establishing a Web connection to the RPS for the defined
Telnet Lockout Duration period. (Default = 60 Seconds.)
5.3.3. Log Configuration
This feature allows you to create records of command activity and temperature readings for the
RPS unit. The Log features are enabled and configured via the System Parameters Menus.
•
Audit Log:
Creates a record of all power switching at the RPS unit, including reboots.
Each Log record includes a description of the activity that caused the power switching, the
username for the account that initiated the power switching or reboot and the time and date
that the power switching or reboot occurred. In addition to power switching activity, the
Audit Log will also include login/logout activity for each user account.
•
Alarm Log:
This feature is not used at this time and is reserved for future firmware
upgrades.
•
Temperature Log:
The Temperature Log provides a record of temperature levels over
time at the RPS unit. Each Log record will include the time and date, and the temperature
reading.