FUNCTION 01 - STAR - DELTA motor start

When the apparatus is powered up

energizes and timing starts immediately.

When set time

has elapsed,

is deactivated.

After a programmable pause

(

) the

contact for delta start (

) is permanently closed.

command

T1

command

T2

command

factory setting 0.5 d -

, which can be modified from 0,1 ÷ 9

tenths of seconds

tenths of seconds

5 - FUNCTION

:

U = Power supply (A1-A2)

T1-T2 = Set time

Control

-

= Relay control output

Symbols used in the graphics

T1

U

T2

Control

Control

4 - ACTIVATION OF PROGRAMMING CYCLE TO CHANGE SETTINGS

To a c t i v a t e t h e

and

previous set-

tings during normal ope-
ration or with device
c y c l e t i m i n g i n p r o-
gress,

p r o-

gramming cycle
change

press the

key for

5 sec. and proceed as
described above for
function selection,

and

.

MODE

time

scale

timer set-

ting

If the programming cycle is activated but no settings are to be
changed, press

to confirm the current programming.

N.B.
cycle in progress

Starting a programming modification procedure interrupts the

, cancelling the timing and deactivating the relay.

d

h

s

X

100

1

MODE

+

OK c

/

_

RESET

Press
5 seconds

Display with timer

C

activated

(fig.

)

During this phase of operation the display shows the following information:

Function number
Symbol

or

lit (indicating which Timer is operating)

Time Clock symbol lit
The figures for timing indicate the time remaining before the current count finishes and the symbol

flashes.

!

!

!

!

F01

T1

T2

flashing

6 - OPERATION

Display with timer not activated

During this phase of operation the display shows the following information:

function number

.

If the setting for

is the same as

, the display will show the set value, the time scale

and indicators

and

will be lit (fig. ).

If the setting for

is different from

, the display shows the two settings (fig . )

alternately for 5 seconds.

!

!

!

F01

Timer 1

Timer 2

T1

T2

A

Timer 1

Timer 2

B

During operation, the relay contact status is indicated by LEDs

and

(LED on = relay contact activated).

N.B.

During the count the time scale automatically adjusts to the remaining time to be displayed.

MODE

+

_

OK c

/

RESET

MODE

+

_

OK c

/

RESET

d

X

100

1

2

A

d

s

1

d

s

2

5 sec.

B

d

h

s

1

C

MODE

+

_

OK c

/

RESET

The manufacturer reserves the right to make all technical and manufacturing modifications deemed necessary without prior notice.

7 - OPERATING TIME COUNTER

Display of operating time

will be lost.
To display RELAY

counter, press the key

for 5 seconds; the

display will show the wording

Operating times are displayed in the

following manner:
from 0 to 9999 the total number of hours is displayed (fig. );
from 10000 to 999900 the multiplier

is switched on

ex. (10000 hours = 100

) (fig.

)

.

A

B

X100

X100

The timer memorizes the count of hours of relay operation;the
memorization is increased by one unit each time an hour
elapses. If a Reset is done before the full hour has elapsed,the increase

ushing the

or

key it goes to

show the RELAY

contact closing time and on the display will appe-

ar

and the corresponding working hours.

+

. P

N.B.: the display will stay on for 10 secondes.

.........

.

.........

Cancelling operating times

The hour count can be reset while the counter

or

, by

pressing the key

again for 5 seconds until the flashing symbols

appear on the display, as shown in fig.

. When the key

is released

the initial display appears (fig. ).

is displayed

C

D

8 - HARDWARE RESET

In the case that the device shows anomalous displays or improper
functioning, insert a thin pointed object (max 1 mm) in the hole of the
panel front, marked

, and press once (fig. )

RESET

E

Hardware resetting does not cancel the settings previously
entered in the memory.

.

OK c

/

OK c

/

OK c

/

RESET

d

h

s

X

1

00

C

h

1

A

B

d

s

1

D

E

MODE

+

_

d

h

s

1

2

MODE

+

OK c

/

_

d

h

s

X

100

1

2

MODE

+

OK c

/

OK c

/

_

RESET

RESET

d

h

s

X

100

1

2

MODE

+

OK c

/

_

RESET

Press
5 seconds

Press
5 seconds

Summary of Contents for 1RT200/MT/MF

Page 1: ...65 C 2 3 LVD EN 61812 1 EMC EN 61812 1 classe di applicazione 2 Tensione di alimentazione Installazione Dimensioni L x P x H Grado di protezione Sezione dei cavi ai morsetti Tipo di uscita Frequenza...

Page 2: ...viene disattivato Dopo una pausa programmabile impostazione di fabbrica 0 5 decimi di secondo modificabile da 0 1 9 decimi di secondo il contatto per l avviamento a triangolo viene chiuso permanentem...

Page 3: ...erminals 17 c ontact NO for command contact NO for command A1 A2 No 18 c No 28 witch mains supply off No ommon for both contacts Important the installation and electrical connections of devices and eq...

Page 4: ...ttings fig alternately for 5 seconds F01 Timer 1 Timer 2 T1 T2 A Timer 1 Timer 2 B During operation the relay contact status is indicated by LEDs and LED on relay contact activated N B During the coun...

Page 5: ...ions commutations Tension d alimentation Installation Dimensions Degr de protection Section maximum des fils aux bornes Type de sortie Plage de r glage de la temporisation T1 Plage de r glage de la te...

Page 6: ...le et les heures de fonctionnement N B la visualisation reste active pendant 10 secondes A B X100 X100 Effacement heures de fonctionnement Pendant la visualisation du compteur ou vous pouvez mettre z...

Page 7: ...lichen Bestimmungen durchgef hrt werden Der Hersteller bernimmt keine Haftung f r die Verwendung von Produkten f r die besondere Umgebungs und oder Installationsbedingungen erf llt werden m ssen Das S...

Page 8: ...Taste und gehen Sie wie bei der oben be s c h r i e b e n e n und MODE Zeitskalaauswahl Schaltuhreinstellung vor 5 Sekunden dr cken OK c HINWEIS Das Anlaufen des nderungsverfahrens der Programmierung...

Page 9: ...mutaci nes conmutaci nes Alimentaci n Instalaci n Dimensiones Grado de protecci n Secci n m xima de los cables a los terminales Tipo de salida Campo de temporizaci n T1 Campo de temporizaci n T2 T Pot...

Page 10: ...ontacto REL sobre la pantalla comparir la indicaci n y las horas de funcionamiento NOTA la visualizaci n dura 10 segundos A X100 B X100 C mo borrar las horas de funcionamiento Durante la visualizaci n...

Reviews: