background image

 

Pertronic Industries Pty Ltd 

2   

0312-PS1-T3 Sounder Issue 1.2, 200902

 

Operation: 

The panel Bell circuit connects to the 

PS1-T3

 Sounder as shown below.   

Bell terminals ‘+’ and ‘-’ connect to the corresponding Sounder ‘+’ and ‘-’ terminals.   
If  the  Bells  are  not  active,  the  panel  monitors  the  Bell  circuit  by  applying  a  negative 
voltage  to  the 

PS1-T3

  ‘+’  terminal.  The  quiescent  current  drawn  by  the 

PS1-T3

  under 

this condition is less than 0.4

µ

A. 

When  the  panel  Bell  circuit  activates,  the  panel  Bell  circuit  voltage  reverses  (applying 
positive  voltage  to  the 

PS1-T3

  ‘+’  terminal),  sounding  the 

PS1-T3

.  The  ‘T3’  tone  is 

generated  if  the  ‘Alert’  terminal is  open  or  J3  link  not  fitted.  If  the  ‘Alert’  terminal  of  the 

PS1-T3

  is  connected  to  0V  (negative)  or  the  J3  link  is  fitted,  the  ‘AS2220’  tone  is 

generated instead. 

PS1-T3 Operation 

Panel Bell Circuit 

Alert Terminal or J3 link 

Tone Generated 

Monitor mode 

Don’t Care 

None 

Active 

Open 

T3-Evacuate 

Active 

0V or link fitted 

AS2220-Evacuate 

 
Connection Diagrams: 

Basic Connection: 

T3 

Evacuation only on Bell Circuit reversal 

 
 
 
 
 
 
 
 
 
 

 

Basic Connection: 

AS2220

 Evacuation on Bell Circuit reversal 

 
 
 
 
 
 
 
 

 
 
 

 
Product Codes: 

 
 

 

Part Code

 

Description

 

PS1-T3 

Sounder, Pert w/o Front Plate – T3 tone 

PS1/2-FCR 

Sounder Cover – Flush Red 

PS1/2-FCW 

Sounder Cover – Flush White 

Reviews: