background image

 

© Pertronic Industries Ltd 

20 

FAAST LT Loop-Based Installation & Maintenance Guide  Iss 1.0, 201701

 

E2d.  Commissioning Tests 

Before performing these  tests ensure  the area  being  protected  is in  its fully  operational state 

– both in terms of 

airflows and cleanliness. For example, any air handling units (AHUs) should be running, all floor and ceiling tiles 
should be installed and any equipment producing a heat load should be in its normal operational mode.  
Results from all tests, particularly details of the test  positions, should be recorded so that they can  be repeated 
during Maintenance.  

(i)  Prescribed  Standard  :

  for  ASD  systems  designed  to  prescribed  standards,  commissioning  tests  should 

include but are not limited to: -  
•  Maximum Smoke Transport Time from last sampling hole in system.  
•  Fault detection, including blockage and rupture of the pipe.  
•  Tests to confirm that Sampling Points are functioning.  

(ii) Performance Based :

 for ASD systems designed to a performance requirement additional performance tests 

should be performed. They should be conducted in accordance with the design requirements. 

a)  Transport Time Measurement 

Maximum transport time is measured by introducing smoke into the furthest Sample Point (or a dedicated test 
point) and measuring the time between first introducing the smoke and observing a “reaction” at the detector.  

b)  Smoke Test: 

The system Alarm response MUST be tested for functionality

 

using smoke 

-  the choice of smoke source is dependent on the

 

installation - Pertronic Industries recommends the use of a 

Smoke Pen (PN: SMOKEPEN). Aerosol smoke is not recommended as it may leave residue inside the pipe  

The procedure for this test depends upon whether the FAAST detector is Loop-Based or Stand-Alone: 

Loop-Based: 

(i)  at the F100 or F120 panel, access Menu \ Status (\ Device) : Loop Address of the FAAST detector. Note 

the PW4 value 

(ii) on  each  Pipe  of  a  multiple  branch  system,  introduce  smoke  into  the  Sampling  Point  furthest  from  the 

detector 

– if the End Cap is configured as a Non-Sensing Point, use the penultimate Sampling Point 

(iii) start  the  Timer  as  the  smoke  enters  the  Sampling  Point,  then  move  to  the  panel  and  note  the  PW4 

value. The smoke must be present for the

 

duration of the test 

(iv) stop  the  Timer  as  the  PW4  value  begins  to  rise  indicating  smoke  has  been  detected 

–  this  is  the 

Transport Time for this Sample Point.  
-  the  Maximum  Transport  Time  shall  be  less  than  the  maximum  time  specified  within  the  design 

documentation/ engineering specifications but must not exceed 90 seconds (NZS4512:2010). 

Where an Alarm indication is used it does not generally include any Alarm delays, which are temporarily set to 
zero for the measurement of Transport Time.  
Measured Transport Time should be compared to the predicted design Transport Time.  

c)  Fault Detection 

Simulate the following faults on the detector and check that the fault is signalled at both FAAST detector

 

and 

at the Fire Panel. 
(i) 

Pipe Flow :

 for each sampling pipe connected to the FAAST unit: 

-  block the pipe and ensure a Low Flow Defect is reported 
-  remove the Endcap and ensure a High Flow Defect is reported 
-  block a single Sampling Point and confirm the Air-Flow indicator responds 
-  block  a  series  of  Sampling  Points  and  record  the  identity  of  each  hole  and  number  (quantity)  required  to 

produce a Low Flow Defect 

– identifying the holes individually provides the ability to replicate later during 

Maintenance 

-  record Flow readings for later reference during Maintenance.  

Note:  A  20%  reduction  in  volumetric  flow  (EN54-20)  is  considered  an  appropriate  Defect  condition. 

Sampling Points do not usually block individually but all become contaminated at similar rates. 

(ii) 

Power Supply

 : 

-  disconnect the battery and verify that a PSU fault is reported 
-  disconnect the Mains supply and verify that a PSU fault is reported.  
(iii) 

Internal Faults :

  

-  disconnect Sounder 1 (Pins 17/18) and verify that a fault is reported 
-  disconnect Sounder 2 (Pins 19/20) and verify that a fault is reported (Dual Channel FAAST Only)

 

d)  Functional Tests 

Commissioning  must  include  sufficient  testing  to  verify  that  Sampling  Points  are  fully  functional.  Careful 
inspection/validation  of  the  sampling  holes  to  confirm  that  they  are  correctly  drilled  and  comparison  of 
measured  transport  times  to  predicted  transport  times  is  often  considered  sufficient  validation,  particularly 
where performance tests are specified.  
-  identify and inspect a sample of Sampling Points and verify they are drilled to the correct size and spacing 
-  measure  the  actual  current  drawn  from  the  power  supply 

–  record  this  and  use  the  Battery  Calculator 

(http://www.pertronic.co.nz/engineering/battery_calc/welcome.php)  to  ensure  the  PSU  and  Battery  are 
appropriate to achieve the required Standby period 

-  activate Configurable Input (Pins 21/22) and verify that it functions as configured 

 
 

 

Summary of Contents for SYSTEM SENSOR FAAST LT Series

Page 1: ...mum Number of Holes See Table 1A Pipe Spec EN54 20 Compliance to EN61386 Crush 1 Impact 1 Temp 31 Outside Pipe Diameter 25mm or 27mm nom Shipping Weight 6 5kg incl detectors Colour Code Key refer to back page Black applies to both FL01nn and FL20nn Series Blue refers to Important Settings which should be verified Figure 1 Dimensions and Knock Outs PARTS LIST Description Quantity FAAST LT Unit 1 Mo...

Page 2: ...e front panel labels fitted This allows the installer to select the language required from the Front Panel Labelling Pack Figure 2 shows where to place the labels Figure 2 Front Panel Label Locations When label A is in place remove the protector from the bottom of the clear cover to stick the cover down as shown in Figure 3 Figure 3 Remove backing tape to stick cover down Cable Access Knock out ca...

Page 3: ...ation Figure 8 Pipe Holes Table 1 Pipe Holes Used for Each FAAST LT Model FAAST LT Model Inlet Pipe Hole Outlet Pipe Hole FL2011EI 1 2 or 1 OR 2 5 FL2012EI 1 2 or 1 OR 2 6 FL2022EI Channel 1 1 2 or 1 OR 2 5 Channel 2 3 4 or 3 OR 4 6 Notes a Unused Pipe Holes MUST be kept sealed b Do NOT glue pipes into Pipe Holes Table 1a Maximum Number of Pipe Holes Allowed Per Channel All figures quoted using hi...

Page 4: ...ulations b Loop wiring must observe the recommendations of the panel manufacturer Notes use the PipeIQ BOM Report to order the Pipe components required to assemble the system use the PipeIQ Pipe Layout Report to assemble the pipe layout Important follow the Pipe Layout report as closely as practical ensure Pipe Lengths are correct ensure Sampling Point holes are drilled at the stated positions ens...

Page 5: ...Set ON in ALARM default Setting the Sensor Addresses Each aspiration channel uses loop communications to report its status information to the CIE Fire Panel As a factory default the unit will report Smoke Alarm and sensor information at an associated Detector address and general Alerts and Faults on a different Module address The default addresses are Channel 1 01 Channel 2 02 Figure 11 Address Sw...

Page 6: ...ed see USB Connection section later in this guide for more information on this and the FAAST LT Advanced Setup and Control Guide EXTERNAL RESET The default setting for the configurable external input is Device Reset terminal block T8 A short circuit connection between these terminals will cause the FAAST LT unit to perform a Reset FRONT PANEL The front panel differs depending on which of the 6 x F...

Page 7: ...ault check filter check pipe network for blockages INPUT 1 Blink External Input fault Not used with default settings SENSOR 2 Blinks Detector communication fault Check detector addresses and installation replace detector ASPIRATOR ON Air Flow sensor fault Try to restart device 1 Blink Flow initialization fault Check filter check pipe network for blockages try to restart device 2 Blinks Fan fault T...

Page 8: ... device is ready for the first digit c press DISABLE to increment the LEDs 1 9 press TEST to select a digit The flashing airflow segment turns ON green and the next segment begins to flash indicating set the next digit When the 4th digit is selected all 4 airflow segments turn OFF if the password is accepted the FAULT indicator remains green and the unit enters MAINTENANCE mode if the password is ...

Page 9: ...ed inside the cabinet at the top of the unit see Figure 10 displayed on Page 4 and are removed as shown in the following sequence Either replace the filter assembly or carefully brush off the accumulated dust Note if replacing the filter remove the foam gasket from the old filter and place onto the new filter When placing the new filter into the slot ensure that the gasket is correctly aligned Ref...

Page 10: ...ctor or available from http www faast detection com contact us download pipeiq Connection to the FAAST LT a Open PipeIQ v2 or greater on the PC by default PipeIQ opens in Configuration mode b Open a project file mdf to continue use one of the following methods i open an existing project configuration mdf file for the FAAST LT or ii start a New Config and add a FAAST LT detector of the type to be i...

Page 11: ...sure Specify the atmospheric pressure in Pascal Both supplies monitored By default the first power supply is monitored to signal a low power Select Yes to monitor the second power supply Power Restart Alert Alert for The device signals the power restart alert for this period Alert till Reset Select to enable alert until the reset is performed Disable Select to disable the power restart alert Trend...

Page 12: ...er ON to reach the configured reference flow Manual the device uses the configured manual speed Fan Speed Drag and set the speed scale for the fan Note The fan speed set here is considered for the calculations of the built network when the fan speed mode is selected as Manual Reference Flow Specify the flow value in litre per minute l min Filter Due Date Specify the due date for the air filters Th...

Page 13: ...activated until a reset is performed No The device automatically deactivates the relay Auxiliary Relay used for Channel 2 Fault Select either of the following Yes The device activates the general fault relay for the faults of channel 1 and faults common to both channels the auxiliary fault relay for faults of channel 2 and for the faults alerts configured to activate auxiliary relay No The auxilia...

Page 14: ...tically change the device real time clock date when the date is in the daylight saving period 1 hour is added No Select No to disable the daylight saving option Auto Select Auto to automatically set the start date as last Sunday of March 02 00 and the end date as the last Sunday of October 02 00 Start Date Select the start date of daylight saving period End Date Select the end date of daylight sav...

Page 15: ... each Sampling Point then use the appropriate Alarm Level as assigned during the PipeIQ Design Calculation f Generally the FAAST LT ALARM level will be 3 4 or 5 The PRE ALARM level may be selected from 1 to a setting less than the ALARM level selected g Use the following Table to determine the appropriate Sensitivity setting to use on an F100 or F120 panel h Configure the Module addresses as Type ...

Page 16: ...Note Click Refresh to obtain the current state of all the relays D1b Smoke Test to perform Smoke Tests a Click Monitoring on the left pane b Select the device to set the actions The Actions tab appears on the right pane c Under Smoke Test set the time for the following two options i Start at a set time Select Start at and select the time to schedule a start time for the smoke test Click Schedule i...

Page 17: ...ce to set the actions The Actions tab appears on the right pane c Under Restart set the following options i Normal select to restart the device in Normal mode ii Maintenance select to restart the device in Maintenance mode d Click Set to apply the restart settings D1g FAAST LT Clock to set the FAAST Clock a Click Monitoring on the left pane b Select the device to set the actions The Actions tab ap...

Page 18: ...og tab click the Events List tab i Select Show All Events to view all the events of the device ii Select Period to view all the events within the specified date From and To dates are available from the drop down calendar iii Click Show The list of events appears Note the Show Last drop down list to select the latest 20 50 100 500 events Below the list of events click First Previous Next and Last t...

Page 19: ...tivity Alarm thresholds are correctly set to ensure that the sensitivity of individual holes meets the minimum performance requirements for individual points Note that this may require reference to the approval compliance notes for the particular ASD system and should also take into account any potential automatic adjustments of the Sensitivity Threshold settings which may occur after commissionin...

Page 20: ...is the Transport Time for this Sample Point the Maximum Transport Time shall be less than the maximum time specified within the design documentation engineering specifications but must not exceed 90 seconds NZS4512 2010 Where an Alarm indication is used it does not generally include any Alarm delays which are temporarily set to zero for the measurement of Transport Time Measured Transport Time sho...

Page 21: ...y Class vs Detection Requirements Colour Code Key When using this manual apply the information which applies to the particular FAAST LT model being installed Black applies to both FL01nn and FL20nn Series FAAST LT detector Blue refers to Important Settings which should be verified While all settings are important many can justifiably remain as the default value but items in Blue should be checked ...

Page 22: ...Humidity Other Power Supply Installed correctly Yes No Pipe Network Installed in Accordance with the PipeIQ design per Pipe Layout Report Yes No Pipe Network Labelled correctly Yes No Describe Any Variations Sensor 1 Module 1 Sensor 2 Module 2 Loop Address L M L M L M L M Sensitivity circle one VEWFD EWFD SFD Class A Class B Class C VEWFD EWFD SFD Class A Class B Class C Threshold Time Delay Day A...

Reviews: