background image

 

© Pertronic Industries Ltd 

FAAST LT Loop-Based Installation & Maintenance Guide  Iss 1.0, 201701

 

X 10

X 1

FL20nnEI Loop-Based Terminal Connections 

Table 2: Wiring Terminal Designations 
(Note - Terminals marked CH2 are only available on 2 channel models) 

No 

Function 

 

Connector 

Ext Power In + 

Primary PSU 

T1 

Ext Power In - 

Aux Power In + 

Not Used in Default 

Aux Power In - 

NC  

Alarm Relay 

CH1   

T2 

NO 

NC  

Alarm Relay 

CH2   

T3 

10 

NO 

11 

NC  

Fault Relay 

CH1   

T4 

12 

13 

NO 

14 

NC  

Fault Relay (AUX) 

CH2   

T5 

15 

16 

NO 

17 

Sounder Output 1 - 

47KΩ EOL Resistor 

T6 

18 

Sounder Output 1 + 

19 

Sounder Output 2 - 

47KΩ EOL Resistor 

T7 

20 

Sounder Output 2 + 

21 

Configurable Input + 

(Reset) 

Default is Active  
= Short-Circuit 
(unsupervised) 

T8 

22 

Configurable Input - 

23 

Not Used 

To Use Isolator 

T9 

24 

Loop Out - 

25 

Loop Switched Out + 

26 

Loop In - 

 

T10 

27 

Loop In + 

28 

Loop Not Switched Out +  Internally Connected to 27 

Table 3: Relays

 

RELAY 

ACTION 

NOTES 

ALARM 1 or 2 

Controlled by the panel when it determines

 

Alarm condition 

has been met. 

Set ON and OFF by panel; not Latched 

FAULT 1 or 2 

When FAULT CONDITION on Ch1 or Ch2 or a common 
FAULT occurs. Fault is also

 

signalled when in Service mode 

and when

 

the device is unpowered 

Fault state is not Latched (default) 

SOUNDER 1 or 2 

Set ON when a channel is in ALARM. Sounder 1 
corresponds to Ch1 and

 

Sounder 2 corresponds to Ch2 

Set ON in ALARM (default) 

 

Setting the Sensor Addresses:

 

Each  aspiration  channel  uses  loop  communications  to  report  its

 

status 

information to the CIE (Fire Panel).  
As  a  factory  default,

 

the  unit  will  report  Smoke  Alarm  and  sensor 

information  at  an

 

associated  Detector  address  and  general  Alerts  and 

Faults on a

 

different Module address. 

The default addresses are: 

Channel 1 = 01 
Channel 2 = 02 

Figure 11: Address Switches 

 

Setting the Detector Addresses: 
Sensor: 

the Sensor address is set 

on  rotary  decade  switches  on  the 
rear  of  the  Laser  (7251)  detector. 
The sensors are located under

 

the 

Sensor  Cover  inside  the  unit  (see 
Figure  10).

 

The  Smoke  Detector 

section  of 

Service

  (refer  to  Page 

9)  shows  how  to  remove  the 
sensors 
As  supplied,  the  default  address 
for  Channel  1  is  Address  1;  in  2 
channel  units,  (or  when  two 
detectors  are  fitted)  the  second 
device is set to Address 2. Hence,

 

Address  99  is  not  valid  for 
Channel  1  on  a  two  sensor 
detector. 

Module: 

The  Module  address  is  set  using 
rotary  decade  address  switches 
located  behind  the

 

door  -  rotate 

the

 

wheels to the desired address. 

The  selected

 

address  refers  to 

Channel 1; on 2 channel

 

units the 

device  assigns  the  next  (+1) 
module

 

address  to  Channel  2 

automatically.  
Note:

 

the  Module  address  only 

responds  to

 

a  panel  poll  when  in 

Normal

 mode. 

Configure  the  Module  as  an 
Output device: RLYM or as AUXM 
if the ability to isolate it as an AUX 
device is required.  
In  Alarm  mode:  By  Sensor,  the 
module provides a detector Defect 
to  the  panel,  eg  for  an  Aspirator 
fault.  
When the door is open the Module 
reports MISSING 

 

Summary of Contents for SYSTEM SENSOR FAAST LT Series

Page 1: ...mum Number of Holes See Table 1A Pipe Spec EN54 20 Compliance to EN61386 Crush 1 Impact 1 Temp 31 Outside Pipe Diameter 25mm or 27mm nom Shipping Weight 6 5kg incl detectors Colour Code Key refer to back page Black applies to both FL01nn and FL20nn Series Blue refers to Important Settings which should be verified Figure 1 Dimensions and Knock Outs PARTS LIST Description Quantity FAAST LT Unit 1 Mo...

Page 2: ...e front panel labels fitted This allows the installer to select the language required from the Front Panel Labelling Pack Figure 2 shows where to place the labels Figure 2 Front Panel Label Locations When label A is in place remove the protector from the bottom of the clear cover to stick the cover down as shown in Figure 3 Figure 3 Remove backing tape to stick cover down Cable Access Knock out ca...

Page 3: ...ation Figure 8 Pipe Holes Table 1 Pipe Holes Used for Each FAAST LT Model FAAST LT Model Inlet Pipe Hole Outlet Pipe Hole FL2011EI 1 2 or 1 OR 2 5 FL2012EI 1 2 or 1 OR 2 6 FL2022EI Channel 1 1 2 or 1 OR 2 5 Channel 2 3 4 or 3 OR 4 6 Notes a Unused Pipe Holes MUST be kept sealed b Do NOT glue pipes into Pipe Holes Table 1a Maximum Number of Pipe Holes Allowed Per Channel All figures quoted using hi...

Page 4: ...ulations b Loop wiring must observe the recommendations of the panel manufacturer Notes use the PipeIQ BOM Report to order the Pipe components required to assemble the system use the PipeIQ Pipe Layout Report to assemble the pipe layout Important follow the Pipe Layout report as closely as practical ensure Pipe Lengths are correct ensure Sampling Point holes are drilled at the stated positions ens...

Page 5: ...Set ON in ALARM default Setting the Sensor Addresses Each aspiration channel uses loop communications to report its status information to the CIE Fire Panel As a factory default the unit will report Smoke Alarm and sensor information at an associated Detector address and general Alerts and Faults on a different Module address The default addresses are Channel 1 01 Channel 2 02 Figure 11 Address Sw...

Page 6: ...ed see USB Connection section later in this guide for more information on this and the FAAST LT Advanced Setup and Control Guide EXTERNAL RESET The default setting for the configurable external input is Device Reset terminal block T8 A short circuit connection between these terminals will cause the FAAST LT unit to perform a Reset FRONT PANEL The front panel differs depending on which of the 6 x F...

Page 7: ...ault check filter check pipe network for blockages INPUT 1 Blink External Input fault Not used with default settings SENSOR 2 Blinks Detector communication fault Check detector addresses and installation replace detector ASPIRATOR ON Air Flow sensor fault Try to restart device 1 Blink Flow initialization fault Check filter check pipe network for blockages try to restart device 2 Blinks Fan fault T...

Page 8: ... device is ready for the first digit c press DISABLE to increment the LEDs 1 9 press TEST to select a digit The flashing airflow segment turns ON green and the next segment begins to flash indicating set the next digit When the 4th digit is selected all 4 airflow segments turn OFF if the password is accepted the FAULT indicator remains green and the unit enters MAINTENANCE mode if the password is ...

Page 9: ...ed inside the cabinet at the top of the unit see Figure 10 displayed on Page 4 and are removed as shown in the following sequence Either replace the filter assembly or carefully brush off the accumulated dust Note if replacing the filter remove the foam gasket from the old filter and place onto the new filter When placing the new filter into the slot ensure that the gasket is correctly aligned Ref...

Page 10: ...ctor or available from http www faast detection com contact us download pipeiq Connection to the FAAST LT a Open PipeIQ v2 or greater on the PC by default PipeIQ opens in Configuration mode b Open a project file mdf to continue use one of the following methods i open an existing project configuration mdf file for the FAAST LT or ii start a New Config and add a FAAST LT detector of the type to be i...

Page 11: ...sure Specify the atmospheric pressure in Pascal Both supplies monitored By default the first power supply is monitored to signal a low power Select Yes to monitor the second power supply Power Restart Alert Alert for The device signals the power restart alert for this period Alert till Reset Select to enable alert until the reset is performed Disable Select to disable the power restart alert Trend...

Page 12: ...er ON to reach the configured reference flow Manual the device uses the configured manual speed Fan Speed Drag and set the speed scale for the fan Note The fan speed set here is considered for the calculations of the built network when the fan speed mode is selected as Manual Reference Flow Specify the flow value in litre per minute l min Filter Due Date Specify the due date for the air filters Th...

Page 13: ...activated until a reset is performed No The device automatically deactivates the relay Auxiliary Relay used for Channel 2 Fault Select either of the following Yes The device activates the general fault relay for the faults of channel 1 and faults common to both channels the auxiliary fault relay for faults of channel 2 and for the faults alerts configured to activate auxiliary relay No The auxilia...

Page 14: ...tically change the device real time clock date when the date is in the daylight saving period 1 hour is added No Select No to disable the daylight saving option Auto Select Auto to automatically set the start date as last Sunday of March 02 00 and the end date as the last Sunday of October 02 00 Start Date Select the start date of daylight saving period End Date Select the end date of daylight sav...

Page 15: ... each Sampling Point then use the appropriate Alarm Level as assigned during the PipeIQ Design Calculation f Generally the FAAST LT ALARM level will be 3 4 or 5 The PRE ALARM level may be selected from 1 to a setting less than the ALARM level selected g Use the following Table to determine the appropriate Sensitivity setting to use on an F100 or F120 panel h Configure the Module addresses as Type ...

Page 16: ...Note Click Refresh to obtain the current state of all the relays D1b Smoke Test to perform Smoke Tests a Click Monitoring on the left pane b Select the device to set the actions The Actions tab appears on the right pane c Under Smoke Test set the time for the following two options i Start at a set time Select Start at and select the time to schedule a start time for the smoke test Click Schedule i...

Page 17: ...ce to set the actions The Actions tab appears on the right pane c Under Restart set the following options i Normal select to restart the device in Normal mode ii Maintenance select to restart the device in Maintenance mode d Click Set to apply the restart settings D1g FAAST LT Clock to set the FAAST Clock a Click Monitoring on the left pane b Select the device to set the actions The Actions tab ap...

Page 18: ...og tab click the Events List tab i Select Show All Events to view all the events of the device ii Select Period to view all the events within the specified date From and To dates are available from the drop down calendar iii Click Show The list of events appears Note the Show Last drop down list to select the latest 20 50 100 500 events Below the list of events click First Previous Next and Last t...

Page 19: ...tivity Alarm thresholds are correctly set to ensure that the sensitivity of individual holes meets the minimum performance requirements for individual points Note that this may require reference to the approval compliance notes for the particular ASD system and should also take into account any potential automatic adjustments of the Sensitivity Threshold settings which may occur after commissionin...

Page 20: ...is the Transport Time for this Sample Point the Maximum Transport Time shall be less than the maximum time specified within the design documentation engineering specifications but must not exceed 90 seconds NZS4512 2010 Where an Alarm indication is used it does not generally include any Alarm delays which are temporarily set to zero for the measurement of Transport Time Measured Transport Time sho...

Page 21: ...y Class vs Detection Requirements Colour Code Key When using this manual apply the information which applies to the particular FAAST LT model being installed Black applies to both FL01nn and FL20nn Series FAAST LT detector Blue refers to Important Settings which should be verified While all settings are important many can justifiably remain as the default value but items in Blue should be checked ...

Page 22: ...Humidity Other Power Supply Installed correctly Yes No Pipe Network Installed in Accordance with the PipeIQ design per Pipe Layout Report Yes No Pipe Network Labelled correctly Yes No Describe Any Variations Sensor 1 Module 1 Sensor 2 Module 2 Loop Address L M L M L M L M Sensitivity circle one VEWFD EWFD SFD Class A Class B Class C VEWFD EWFD SFD Class A Class B Class C Threshold Time Delay Day A...

Reviews: